2002-06-28 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) PER TABLE 403.1 A DRINKING FOUNTAIN
 AND A SERVICE SINK ARE REQUIRED. IF SAID
 FIXTURES ARE LOCATED IN THE COMMON AREA
 PLEASE CALL THEM OUT ON THE PLANS.
 2) SHT A-3.0 ICE MAKER. SUBMIT DETAIL
 SHOWING HOW THE ICE MAKER SHALL BE
 DRAINED. IF CONNECTED WITH A PUMP AN AIR
 GAP FITTING SHALL BE REQUIRED LIKE THE
 DISHWASHER.
 3) SHT P-1 WATER ISOMETRIC, WATER HAMMER
 ARRESTOR SHALL BE LOCATED NEAR THE FIX-
 TURES IN AN "EFFECTIVE RANGE" PER PDI-WH
 201 AND MANUF INSTALLATION INSTRUCTIONS
 NOT AT TOP OF DROP AS SHOWN.
 4) SHT P-1 WATER ISOMETRIC, PLEASE PRO-
 VIDE MANUFACTURE INFORMATION FOR INSTA-
 HOT. PRODUCT APPROVAL REQUIRES LISTING
 FROM AN APPROVED TESTING AGENCY. (UL)
 5) SHT P-1 PLUMBING NOTES #13 AIR CHAMB-
 ERS NOT APPROVED. DELETE NOTE.
  
 REVIEW BY KEN STEVENS