| Plan Review Notes For Permit 02060579 |
| Permit Number |
02060579 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-14 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT FOR REVIEW. | | | | | | 1} WHAT IS THE GENERATORS PRIME MOVER? | | | IF FUEL SHOW TANK LOCATION. | | | | | | 2} GIVE GENERATOR OUTPUT-KVA,VOLTS,PHASE | | | | | | 3} INDICATE HOW GENERATOR IS GROUNDED. | | | | | | 4} IS GENERATOR BEING USED AS A | | | SEPERATELY DERIVED SYSTEM? | | | | | | 5} WHERE DO CONDUITS 4,5 & 6 GO? | | | | | | 6} SHOW PHYSICAL LOCATION OF THE | | | GENERATOR AND ANY FUEL TANKS BEING | | | USED,ON A DRAWING. | | | | | | 7} SHOW GROUPING OF DISCONNECTS ON | | | DRAWING. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 |
|