Plan Review Notes
Plan Review Notes For Permit 02060575
Permit Number 02060575
Review Stop P
Sequence Number 2
Notes
Date Text
2002-07-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHOWER IN CABANA BATH AND TUB IN BATH
 #3 NOT VENTED. THE WET VENT SHALL BE
 CONSIDERED THE VENT FOR THE FIXTURES AND
 SHALL EXTEND FROM THE CONNECTION OF THE
 DRY VENT ALONG THE DIRECTION OF THE FLOW
 IN THE DRAIN PIPE TO THE MOST DOWNSTREAM
 FIXTURE DRAIN CONNECTION TO THE HORIZ-
 ONTAL BRANCH DRAIN. 909.1 SINCE THE DRY
 VENT STARTS ABOVE THE LAVS AND THE LAVS
 ARE THE MOST DOWNSTREAM FIXTURE DRAIN
 CONNECTION, THE SHOWER/TUB ARE NOT VENT-
 ED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377