| Plan Review Notes For Permit 02060575 |
| Permit Number |
02060575 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-07-24 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHOWER IN CABANA BATH AND TUB IN BATH | | | #3 NOT VENTED. THE WET VENT SHALL BE | | | CONSIDERED THE VENT FOR THE FIXTURES AND | | | SHALL EXTEND FROM THE CONNECTION OF THE | | | DRY VENT ALONG THE DIRECTION OF THE FLOW | | | IN THE DRAIN PIPE TO THE MOST DOWNSTREAM | | | FIXTURE DRAIN CONNECTION TO THE HORIZ- | | | ONTAL BRANCH DRAIN. 909.1 SINCE THE DRY | | | VENT STARTS ABOVE THE LAVS AND THE LAVS | | | ARE THE MOST DOWNSTREAM FIXTURE DRAIN | | | CONNECTION, THE SHOWER/TUB ARE NOT VENT- | | | ED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|