| 2002-07-15 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) PROVIDE A SOIL BEARING REPORT PER |
| | CITY AMENDMENTS TO THE 2001 FBC 1804.2.2 |
| | |
| | 3) INDICATE THE APPLICABLE INTERNAL |
| | PRESSURE COEFFICIENT AND THE BASIC WIND |
| | PRESSURE ON THE PLANS AS REQUIRED BY THE |
| | FBC SEC. 1606.1.7. |
| | |
| | 4) THE CONDITIONED AREA ON THE PLANS IS |
| | DIFFERENT FROM THE AREA LISTED ON THE |
| | ENERGY FORM. PLEASE CORRECT. |
| | |
| | 5) THE AREA UNDER ATTIC LISTED ON THE |
| | ENERGY CALCS DOES NOT APPEAR TO INCLUDE |
| | THE BONUS ROOM. THE ADJACENT WOOD FRAME |
| | WALL AREA IS INCORRECT. PLEASE REVIEW |
| | AND CORRECT. |
| | |
| | 6) PLEASE CORRECT #1 UNDER FOUNDATION |
| | NOTES TO 0.006 POLYETHELENE (6 MIL.) AS |
| | REQUIRED BY FBC 1909.2. |
| | |
| | 7) OPENINGS FROM A GARAGE DIRECTLY INTO |
| | A ROOM USED FOR SLEEPING PURPOSES IS NOT |
| | PERMITTED PER FBC 411.2.8. |
| | |
| | 8) THE WINDOW (H) IN THE FIRST BATH ROOM |
| | IS REQUIRED TO HAVE TEMPERED GLASS PER |
| | FBC 2405.2.1. |
| | |
| | 9) PLEASE CHANGE NOTE 6 UNDER NOTES ON |
| | SHEET A-2 TO REFERENCE THE FLORIDA |
| | PLUMBING CODE. |
| | |
| | 10) THE NAIL SIZE AND SPACING LISTED FOR |
| | THE SECOND FLOOR DIAPHRAGM IN SECTION 2 |
| | SHEET S-2 DOES NOT CORRESPOND WITH THE |
| | DIAPHRAGM SCHEDULE. PLEASE CORRECT. |
| | |
| | 11) INDICATE ON THE PLANS THAT THE BONUS |
| | ROOM WALLS ARE INSULATED. |
| | |
| | 12) INDICATE HOW THE FIREBLOCKING THAT |
| | IS REQUIRED BY FBC 2305.1.4 AT THE TOP |
| | OF THE STAIR RUN WILL BE ACHIEVED. |
| | |
| | 13) INDICATE THE DRAFTSTOPPING LOCATIONS |
| | AND MATERIAL FOR THE ROOF/CEILING |
| | ASSEMBLY AS REQUIRED BY FBC 2305.2.2. |
| | |
| | 14) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - DOUBLE FRONT DOORS WITHOUT SIDELITES |
| | - STRUCTURAL MULLIONS (EXPIRED) |
| | - SINGLE HUNG WINDOWS (THE COVER PAGE |
| | DOES NOT GO WITH THE REST OF THE PAGES) |
| | |
| | 15) PROVIDE AN INSTALLATION SCHEDULE AND |
| | KEY PLAN FOR THE STORM PANELS. INDICATE |
| | THE TYPE FASTENER AND MOUNTING OPTIONS |
| | THAT WILL BE USED (CIRCLE OR HIGHLIGHT |
| | THE APPROPRIATE ITEMS ON THE APPROVED |
| | DRAWINGS). THIS INFORMATION IS REQUIRED |
| | AT TIME OF PERMIT OR A SEPARATE PERMIT |
| | WITH ADDITIONAL FEES WILL BE REQUIRED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |