| Plan Review Notes For Permit 02060568 |
| Permit Number |
02060568 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-08-05 00:00:00 | PROVISO:MECHANICAL PERMIT 02060612 | | | | | | WHERE MULTIPLE AIR HANDLING SYSTEMS | | | SHARE COMMON SUPPLY OR RETURN AIR DUCTS | | | OR PLENUMS WITH A COMBINED DESIGN | | | CAPACITY GREATER THAN 2,000 CFM, THE | | | RETURN AIR & SUPPLY AIR SYSTEM SHALL BE | | | PROVIDED WITH SMOKE DETECTORS IN | | | ACCORDANCE WITH SECTION 606.2.1. | | | | | | SMOKE DETECTORS SHALL BE INSTALLED | | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | | AIR DUCT. 2001 FBC(M) 606.2.1OR | | | UPON ACTIVATION, THE SMOKE DETECTORS | | | SHALL SHUTDOWN THE AIR DISTRIBUTION | | | SYSTEM. 2001 FBC(M) 606.4 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|