| 2002-07-06 00:00:00 | CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-REVISE ATTIC SIZE. 36"MIN. SEC 2309.6 |
| | 3-CLARIFY SIZE OF EGRESS WINDOWS. 24SH |
| | AND 34SH WINDOWS DON'T MEET THE MIN. |
| | CLEAR HEIGHT & CLEAR OPENING REQUIRED |
| | BY SEC. 1005.4.4 FBC 2001. ARE THESE |
| | CUSTOM MADE WINDOWS? |
| | 4-SPECIFY FIREBLOCKING MATERIAL AND |
| | LOCATION AT STAIRS. SEC. 2305 FBC. |
| | NOTE: FIREBLOCKING AND DRAFTSTOPPING |
| | ARE TWO DIFFERENT THINGS. |
| | 5-SPECIFY FIRECUT AT MASONRY WALL AS |
| | REQUIRED BY SEC. 2305.4 FBC 2001. |
| | 6-PROVIDE SOIL TEST REPORT. |
| | 7-STORM SHUTTERS: |
| | A)PROVIDE COMPLETE INSTALLATION SCHEDULE |
| | AND KEY PLAN. SEE CITY SAMPLE. |
| | B)CLEARLY INDICATE ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS & ANCHOR TYPE AND |
| | SPACING TO BE USED ACCORDING TO THE |
| | MEAN ROOF HEIGHT, DESIGN PRESSURES, |
| | EDGE DISTANCE, PANEL SPAN, CONNECTION |
| | TYPE AND STRUCTURE TO BE ATTACHED TO |
| | (CONCRETE BLOCK OR CONCRETE, OR WOOD) |
| | 8-PROVIDE PRODUCT APPROVAL FOR: |
| | A)SINGLE ENTRY DOOR A SHOWN ON PLANS. |
| | B)COMPLETE PAN AMERICAN WINDOW MULLION |
| | PRODUCT APPROVAL. |
| | C)ARCHED WINDOW NEED LEGIBLE DRAWINGS. |
| | D)SINGLE HUNG PRODUCT APPROVAL REPORT |
| | DOESN'T MATCH DRAWINGS SUBMITTED. |
| | E)ONE HR FIRE RATED GLASS BLOCK ASSEMBLY |
| | 9-PROVIDE UPDATED ORIGINAL LETTER FOR |
| | MASONRY USED ADDRESSED TO THE CITY OF |
| | W.P.B. AND THE CONTRACTOR AND SPECIFY |
| | THE PROJECT WHERE IS GOING TO BE USED. |
| | 10-SHEET C-1 IS MISSING THE INTERNAL |
| | PRESSURE COEFFICIENT AS REQUIRED BY |
| | SECTION 1606.1.7 FBC 2001. |
| | 11-PROVIDE GABLE END DETAIL SHOWING |
| | STRUCTURAL CONTINUITY AS REQUIRED ON |
| | SECTION 2117 FBC 2001. |
| | 12-REVISE GLASS BLOCK DETAIL. NEED 1 HR |
| | FIRE RATED ASSEMBLY AS REQUIRED BY |
| | TABLE 600 FBC 2001. SEE UL LISTING. |
| | 13-MASTER BEDROOM TO HAVE DOOR WITH 29" |
| | MIN. CLEAR OPENING. SEC. 11-11 FBC. |
| | 14-PROVIDE ATTIC ACCESS ABOVE FRONT AREA |
| | OF GARAGE. SEC. 2309.6 FBC 2001. |
| | 15-SEE PLANS FOR ADDITIONAL COMMENTS AND |
| | RETURN REVIEWED SET TO EXPEDITE REVIEW |
| | 16-SPECIFY SUPPORTS FOR CONCRETE SLAB |
| | WWM. SEE SEC. 1909.3 FBC 2001. |
| | 17-CONNECTOR SPECIFIED FOR FRONT FRAMED |
| | WALL ARE FOR WOOD TO CONCRETE, NOT FOR |
| | WOOD TO WOOD APPLICATION. REVISE AS |
| | REQUIRED. SEE SHEET S-1 FOR COMMENTS. |