| 2002-07-10 00:00:00 | CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-ENTRY DOORS DON'T PROVIDE THE 32" MIN. |
| | CLEAR OPENING REQUIRED BY TABLE 1004 |
| | FBC 2001. REVISE AS REQUIRED. |
| | 3-ENERGY CALCULATIONS: |
| | A)THERE IS NOT ADJACENT FRAME WALL. SEE |
| | PLANS AND REVISE AS REQUIRED. |
| | B)OWNER/AGENT TO DATE BOTTOM OF FORM TOO |
| | 4-WINDOW BY ENTRY PORCH EXCEEDS THE MAX. |
| | PERCENTAGE OF OPENINGS ALLOWED BY |
| | TABLE 600 FBC 2001. REVISE AS REQUIRED |
| | 5-SPECIFY FIREBLOCKING MATERIAL AND |
| | LOCATION AT STAIRS. SEC. 2305 FBC 2001 |
| | **NOTE: FIREBLOCKING & DRAFSTOPPING ARE |
| | 2 DIFFERENT THINGS. |
| | 6-SPECIFY FIRECUT AT MASONRY WALL AS |
| | REQUIRED BY SEC. 2305.4 FBC 2001. |
| | 7-2ND FL. FRAMING PLAN: SPECIFY MATERIAL |
| | & LOCATION OF DRAFSTOPPING AS REQUIRED |
| | BY SEC. 2305.2.2 FBC 2001. |
| | 8-PROVIDE SOIL TEST REPORT. |
| | 9-STORM SHUTTERS: |
| | A)PROVIDE COMPLETE INSTALLATION SCHEDULE |
| | AND KEY PLAN. SEE CITY COPY. |
| | B)CLEARLY INDICATE ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR TYPE & |
| | SPACING TO BE USED ACCORDING TO THE |
| | MEAN ROOF HEIGHT, DESIGN PRESSURES, |
| | EDGE DISTANCE, PANEL SPAN, CONNECTION |
| | TYPE AND STRUCTURE TO BE ATTACHED TO |
| | (CONCRETE BLOCK OR CONCRETE). |
| | 10-PROVIDE PRODUCT APPROVAL FOR: |
| | A)ENTRY DOORS AS SHOWN ON PLANS. |
| | B)COMPLETE PANAMERICAN WINDOW MULLION |
| | PRODUCT APPROVAL. |
| | C)SINGLE HUNG WINDOW PRODUCT APPROVAL |
| | DOESN'T MATCH DRAWINGS. |
| | |
| | 11-SHEET C-1 IS MISSING THE INTERNAL |
| | PRESSURE COEFFICIENT AS REQUIRED BY |
| | SEC. 1606.1.7 FBC 2001. |
| | 12-APPROVED PRODUCT APPROVAL ARE STAMPED |
| | ALL OTHERS ARE RETURNED. SEE COMMENTS |
| | ON YELLOW STICKERS. |