| Date |
Text |
| 2002-08-13 00:00:00 | CHECKLIST: |
| | 1-PROVIDE COMPLETE DETAILS AND SPECS FOR |
| | GABLE END SECTION AT FRONT ELEVATION. |
| | CLARIFY HOW DOES THE HALF MASONRY, |
| | HALF WOOD FRAMING GABLE END WORKS. |
| | PROVIDE ENGINEER ANALYSIS SHOWING THE |
| | TRANSITION OF THE WIND LOADS TO THE |
| | SHEARWALLS & ROOF. SEE SEC. 1606.2.4. |
| | ALSO, SHOW HOW IS THE GABLE END STRUC- |
| | TURALLY CONTINUOUS AS REQUIRED BY SEC |
| | 2117 AND 2313 FBC 2001. |
| | 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 3-PROVIDE SOIL TEST REPORT |
| | 4-PROVIDE COMPLETE & CORRECT INFORMATION |
| | FOR STORM SHUTTERS OR APPLY FOR A |
| | SEPARATE PERMIT. NEED: A)LEGIBLE DWGS |
| | THAT MATCH PRODUCT APPROVAL. B)REVISE |
| | KEY PLAN & INSTALLATION SCHEDULE TO |
| | MATCH OPENINGS SIZE, ETC. C)VERIFY IF |
| | 32" LONG SHUTTERS WIL BE ADEQUATE. |
| | 5-PROVIDE PRODUCT APPROVAL FOR: |
| | A)SINGLE ENTRY DOOR WITH ONE SIDELITE |
| | ASSEMBLY AS SHOWN ON PLANS. NOTE: NEED |
| | LEGIBLE DRAWINGS ALSO. |
| | B)SINGLE HUNG WINDOWS W/ MATCHING DWGS. |
| | C)GLASS BLOCK UL LISTING AND COMPLETE |
| | SPECIFICATIONS FOR ONE HOUR FIRE RATED |
| | ASSEMBLY AS REQ'D BY TABLE 600 FBC. |
| | D)FIXED RECTANGULAR WINDOW WITH MATCHING |
| | DRAWINGS. NOTE: SEE SIZE ON PLANS AND |
| | ELEVATIONS. CLARIFY IF THERE ARE THREE |
| | FIXED WINDOWS MULLED TOGETHER OR IF |
| | IT'S ONE BIG RECTANGULAR WINDOW. |
| | 6-PROVIDE GLASS BLOCK ASSEMBLY DETAIL |
| | FOR ONE HOUR FIRE RATING. SEE UL SPECS |
| | FOR PRODUCT APPROVAL SUBMITTED. |
| | 7-SEE PLANS FOR ADDITIONAL COMMENTS AND |
| | RETURN REVIEWED SET AFTER CORRECTIONS |
| | ARE DONE TO ORIGINALS TO EXPEDITE |
| | REVIEW. |
| | 8-DRAWINGS 9/14 IS NOT CLEAR. IT DOESN'T |
| | SHOW THE STORM PANEL GLASS SEPARATION, |
| | EDGE DISTANCE AND TYPE OF TRACK TO |
| | RECEIVE THE STORM PANELS. SEE PRODUCT |
| | APPROVAL TO VERIFY THAT THIS TYPE OF |
| | INSTALLATION WILL WORK. |
| | 9-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| | FIXED WINDOW. DETAIL SUBMITTED DOESN'T |
| | APPLY. WINDOW IS LOCATED ON MASONRY |
| | WALL, NOT IN FRAMED WALL. |
| | 10-CLEARLY IDENTIFY ROOF ZONE #3 ON ROOF |
| | FRAMING PLAN. NOTE: ZONE IS NOT ONLY |
| | AT GABLE ENDS. SEE TABLE 2306.1 CITY |
| | AMENDMENTS TO FBC 2001. |