Plan Review Notes
Plan Review Notes For Permit 02060554
Permit Number 02060554
Review Stop R
Sequence Number 2
Notes
Date Text
2002-08-13 00:00:00CHECKLIST:
 1-PROVIDE COMPLETE DETAILS AND SPECS FOR
 GABLE END SECTION AT FRONT ELEVATION.
 CLARIFY HOW DOES THE HALF MASONRY,
 HALF WOOD FRAMING GABLE END WORKS.
 PROVIDE ENGINEER ANALYSIS SHOWING THE
 TRANSITION OF THE WIND LOADS TO THE
 SHEARWALLS & ROOF. SEE SEC. 1606.2.4.
 ALSO, SHOW HOW IS THE GABLE END STRUC-
 TURALLY CONTINUOUS AS REQUIRED BY SEC
 2117 AND 2313 FBC 2001.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE SOIL TEST REPORT
 4-PROVIDE COMPLETE & CORRECT INFORMATION
 FOR STORM SHUTTERS OR APPLY FOR A
 SEPARATE PERMIT. NEED: A)LEGIBLE DWGS
 THAT MATCH PRODUCT APPROVAL. B)REVISE
 KEY PLAN & INSTALLATION SCHEDULE TO
 MATCH OPENINGS SIZE, ETC. C)VERIFY IF
 32" LONG SHUTTERS WIL BE ADEQUATE.
 5-PROVIDE PRODUCT APPROVAL FOR:
 A)SINGLE ENTRY DOOR WITH ONE SIDELITE
 ASSEMBLY AS SHOWN ON PLANS. NOTE: NEED
 LEGIBLE DRAWINGS ALSO.
 B)SINGLE HUNG WINDOWS W/ MATCHING DWGS.
 C)GLASS BLOCK UL LISTING AND COMPLETE
 SPECIFICATIONS FOR ONE HOUR FIRE RATED
 ASSEMBLY AS REQ'D BY TABLE 600 FBC.
 D)FIXED RECTANGULAR WINDOW WITH MATCHING
 DRAWINGS. NOTE: SEE SIZE ON PLANS AND
 ELEVATIONS. CLARIFY IF THERE ARE THREE
 FIXED WINDOWS MULLED TOGETHER OR IF
 IT'S ONE BIG RECTANGULAR WINDOW.
 6-PROVIDE GLASS BLOCK ASSEMBLY DETAIL
 FOR ONE HOUR FIRE RATING. SEE UL SPECS
 FOR PRODUCT APPROVAL SUBMITTED.
 7-SEE PLANS FOR ADDITIONAL COMMENTS AND
 RETURN REVIEWED SET AFTER CORRECTIONS
 ARE DONE TO ORIGINALS TO EXPEDITE
 REVIEW.
 8-DRAWINGS 9/14 IS NOT CLEAR. IT DOESN'T
 SHOW THE STORM PANEL GLASS SEPARATION,
 EDGE DISTANCE AND TYPE OF TRACK TO
 RECEIVE THE STORM PANELS. SEE PRODUCT
 APPROVAL TO VERIFY THAT THIS TYPE OF
 INSTALLATION WILL WORK.
 9-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 FIXED WINDOW. DETAIL SUBMITTED DOESN'T
 APPLY. WINDOW IS LOCATED ON MASONRY
 WALL, NOT IN FRAMED WALL.
 10-CLEARLY IDENTIFY ROOF ZONE #3 ON ROOF
 FRAMING PLAN. NOTE: ZONE IS NOT ONLY
 AT GABLE ENDS. SEE TABLE 2306.1 CITY
 AMENDMENTS TO FBC 2001.