| 2002-07-08 00:00:00 | CHECKLIST: |
| | 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 2-REVISE ATTIC ACCESS SIZE. 36"MIN. NOT |
| | 30". SEC 2309.6 FBC 2001. |
| | 3-CLARIFY SIZE OF 34SH WINDOW. TYPICALLY |
| | 34SH WINDOW DOESN'T ALLOW 24" CLEAR HT |
| | OPENING. SEC. 1005.4.4 FBC 2001. |
| | IS THIS A CUSTOM MADE WINDOW? |
| | 4-PROVIDE SOIL TEST REPORT. |
| | 5-STORM SHUTTERS: |
| | A)PROVIDE COMPLETE INSTALLATION SCHEDULE |
| | AND KEY PLAN. SEE CITY SAMPLE. |
| | B)CLEARLY INDICATE ON DRAWINGS SPECIFIC |
| | MOUNTING CONDITIONS AND ANCHOR TYPE & |
| | SPACING TO BE USED ACCORDING TO THE |
| | MEAN ROOF HEIGHT, DESIGN PRESSURES, |
| | EDGE DISTANCE, PANEL SPAN, CONNECTION |
| | TYPE AND STRUCTURE TO BE ATTACHED TO |
| | (CONCRETE BLOCK OR CONCRETE) |
| | 6-PROVIDE PRODUCT APPROVAL FOR: |
| | A)SINGLE ENTRY DOOR WITH ONE SIDELITE AS |
| | SHOWN ON PLANS & WITH LEGIBLE AND |
| | COMPLETE DRAWINGS (NOT HALF COPIES). |
| | B)COMPLETE PAN AMERICAN WINDOW MULLION. |
| | C)SINGLE HUNG PRODUCT APPROVAL REPORT |
| | DOESN'T MATCH DRAWINGS SUBMITTED. |
| | D)1 HR FIRE RATED GLASS BLOCK ASSEMBLY. |
| | E)FIXED RECTANGULAR WINDOW WITH THE |
| | SIZE SHOWN ON PLANS. |
| | |
| | 7-PROVIDE UPDATED ORIGINAL LETTER FOR |
| | MASONRY USED AND ADDRESSED TO THE CITY |
| | OF W.P.B. AND THE CONTRACTOR. ALSO, |
| | SPECIFIED PROJECT DELIVERED TO. |
| | 8-SHEET C-1 IS MISSING THE INTERNAL |
| | PRESSURE COEFFICIENT AS REQUIRED BY |
| | SEC. 1606.1.7 FBC 2001. |
| | 9-PROVIDE COMPLETE GABLE END SECTION/ |
| | DETAIL AT FRONT ELEVATION SHOWING |
| | CONTINUITY REQUIRED BY SEC. 2117.1.2 |
| | FBC 2001. |
| | 10-REVISE GLASS BLOCK DETAILS. NEED ONE |
| | HR FIRE RATED ASSEMBLY AS REQUIRED BY |
| | TABLE 600 FBC 2001. SEE UL LISTING FOR |
| | ONE HR FIRE RATED ASSEMBLY SPECS. |
| | 11-SEE PLANS FOR ADDITIONAL COMMENTS AND |
| | RETURN REVIEWED SET TO EXPEDITE REVIEW |
| | 12-SPECIFY SUPPORTS FOR CONCRETE SLAB |
| | WWM. SEE SECTION 1909.3 FBC 2001. |
| | 13-CLARIFY NOTE #42 ON SHEET A-1. SEE |
| | STORM SHUTTERS PRODUCT APPROVAL TO |
| | VERIFY IF PROPOSED INSTALLATION WORKS. |
| | CONSIDER THE REQUIRED GLASS DISTANCE. |
| | 14-ENERGY CALCULATIONS: REVISE UNDER |
| | ATTIC AREA. SEE SEC. 602.1.ABC.1.2 OF |
| | CHAPTER 13 FBC 2001. |
| | 15-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| | FIXED WINDOWS AS REQUIRED ON PRODUCT |
| | APPROVAL SUBMITTED. |