Plan Review Notes
Plan Review Notes For Permit 02060554
Permit Number 02060554
Review Stop R
Sequence Number 1
Notes
Date Text
2002-07-08 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-REVISE ATTIC ACCESS SIZE. 36"MIN. NOT
 30". SEC 2309.6 FBC 2001.
 3-CLARIFY SIZE OF 34SH WINDOW. TYPICALLY
 34SH WINDOW DOESN'T ALLOW 24" CLEAR HT
 OPENING. SEC. 1005.4.4 FBC 2001.
 IS THIS A CUSTOM MADE WINDOW?
 4-PROVIDE SOIL TEST REPORT.
 5-STORM SHUTTERS:
 A)PROVIDE COMPLETE INSTALLATION SCHEDULE
 AND KEY PLAN. SEE CITY SAMPLE.
 B)CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 EDGE DISTANCE, PANEL SPAN, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO
 (CONCRETE BLOCK OR CONCRETE)
 6-PROVIDE PRODUCT APPROVAL FOR:
 A)SINGLE ENTRY DOOR WITH ONE SIDELITE AS
 SHOWN ON PLANS & WITH LEGIBLE AND
 COMPLETE DRAWINGS (NOT HALF COPIES).
 B)COMPLETE PAN AMERICAN WINDOW MULLION.
 C)SINGLE HUNG PRODUCT APPROVAL REPORT
 DOESN'T MATCH DRAWINGS SUBMITTED.
 D)1 HR FIRE RATED GLASS BLOCK ASSEMBLY.
 E)FIXED RECTANGULAR WINDOW WITH THE
 SIZE SHOWN ON PLANS.
  
 7-PROVIDE UPDATED ORIGINAL LETTER FOR
 MASONRY USED AND ADDRESSED TO THE CITY
 OF W.P.B. AND THE CONTRACTOR. ALSO,
 SPECIFIED PROJECT DELIVERED TO.
 8-SHEET C-1 IS MISSING THE INTERNAL
 PRESSURE COEFFICIENT AS REQUIRED BY
 SEC. 1606.1.7 FBC 2001.
 9-PROVIDE COMPLETE GABLE END SECTION/
 DETAIL AT FRONT ELEVATION SHOWING
 CONTINUITY REQUIRED BY SEC. 2117.1.2
 FBC 2001.
 10-REVISE GLASS BLOCK DETAILS. NEED ONE
 HR FIRE RATED ASSEMBLY AS REQUIRED BY
 TABLE 600 FBC 2001. SEE UL LISTING FOR
 ONE HR FIRE RATED ASSEMBLY SPECS.
 11-SEE PLANS FOR ADDITIONAL COMMENTS AND
 RETURN REVIEWED SET TO EXPEDITE REVIEW
 12-SPECIFY SUPPORTS FOR CONCRETE SLAB
 WWM. SEE SECTION 1909.3 FBC 2001.
 13-CLARIFY NOTE #42 ON SHEET A-1. SEE
 STORM SHUTTERS PRODUCT APPROVAL TO
 VERIFY IF PROPOSED INSTALLATION WORKS.
 CONSIDER THE REQUIRED GLASS DISTANCE.
 14-ENERGY CALCULATIONS: REVISE UNDER
 ATTIC AREA. SEE SEC. 602.1.ABC.1.2 OF
 CHAPTER 13 FBC 2001.
 15-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR
 FIXED WINDOWS AS REQUIRED ON PRODUCT
 APPROVAL SUBMITTED.