| 2002-07-08 00:00:00 | BUILDING DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) STRUCTURE IS LOCATED IN AN "A8" FLOOD |
| | ZONE, AN ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. |
| | |
| | 3) PROVIDE A SOIL BEARING REPORT PER |
| | CITY AMENDMENTS TO THE 2001 FBC 1804.2.2 |
| | |
| | 4) INDICATE THE APPLICABLE INTERNAL |
| | PRESSURE COEFFICIENT AND THE BASIC WIND |
| | PRESSURE ON THE PLANS AS REQUIRED BY THE |
| | FBC SEC. 1606.1.7. |
| | |
| | 5) PLEASE CORRECT #1 UNDER FOUNDATION |
| | NOTES TO 0.006 POLYETHELENE (6 MIL.) AS |
| | REQUIRED BY FBC 1909.2. |
| | |
| | 6) OPENINGS FROM A GARAGE DIRECTLY INTO |
| | A ROOM USED FOR SLEEPING PURPOSES IS NOT |
| | PERMITTED PER FBC 411.2.8. THE BONUS |
| | ROOM IS REQUIRED TO BE PERMANENTLY |
| | MARKED ON THE PLANS THAT IT IS NOT TO BE |
| | USED FOR SLEEPING PURPOSES. |
| | |
| | 7) THE WINDOW (H) IN THE FIRST FLOOR |
| | BATH ROOM IS REQUIRED TO HAVE TEMPERED |
| | GLASS PER 2405.2.1. |
| | |
| | 8) PLEASE CHANGE NOTE 6 UNDER GENERAL |
| | NOTES ON SHEET A-2 TO REFERENCE THE |
| | 2001 FLORIDA PLUMBING CODE. |
| | |
| | 9) PLEASE PROVIDE SURVEY WITH THE SIDE |
| | SET BACK DIMENSIONS LISTED. |
| | |
| | 10) THE NAIL SIZE AND SPACING LISTED FOR |
| | THE SECOND STORY FLOOR DIAPHRAM AT |
| | SECTION 2 ON SHEET S-2 DOES NOT |
| | CORRESPOND TO THAT LISTED IN THE |
| | DIAPHRAM SCHEDULE. PLEASE CORRECT. |
| | |
| | 11) THE A/C AREA LISTED ON THE PLANS |
| | DIFFERS FROM THE CONDITIONED AREA GIVEN |
| | ON THE ENERGY CALCULATIONS. PLEASE |
| | CORRECT. |
| | |
| | 12) INDICATE ON THE PLANS THAT THE BONUS |
| | ROOM WALLS ARE INSULATED. |
| | |
| | 13) PLEASE REVIEW THE AREA OF WOOD FRAME |
| | WALL ADJACENT TO UNCONDITIONED SPACE |
| | GIVEN ON THE ENERGY FORM AND CORRECT. |
| | |
| | 14) INDICATE HOW FIREBLOCKING AT THE TOP |
| | OF THE STAIR RUN WILL BE ACHIEVED. SEE |
| | FBC 2305.1.4. |
| | |
| | 15) INDICATE DRAFTSTOPPING LOCATIONS AND |
| | MATERIAL FOR THE ROOF/CEILING ASSEMBLY |
| | AS REQUIRED BY FBC 2305.2.2. |
| | |
| | 16) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - FRONT DOOR WITHOUT SIDELITES |
| | - STRUCTURAL MULLIONS |
| | - SINGLE HUNG WINDOWS (THE COVER PAGE OF |
| | THOSE SUBMITTED HAS A DIFFERENT |
| | ACCEPTANCE NUMBER THAN THE OTHER PAGES. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)659-8096 EXT.8202 |