| 2002-08-08 00:00:00 | CHECKLIST: |
| | 1-PROVIDE ENGINEERING CALCULATIONS AND |
| | DIAGRAMS SHOWING HOW ARE EXTERIOR |
| | WALLS DESIGNED FOR LATERAL STABILITY |
| | (SHEAR WALLS) SEC. 2105 FBC AND FOR |
| | LATERAL SUPPORT AS REQUIRED ON SECTION |
| | 2107 FBC. CLARIFY HOW ARE WIND LOADS |
| | TRANSFERED TO THE ROOF AND FLOOR |
| | DIAPHRAGMS. (SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | 2-CLARIFY CONNECTION AT POST P1. PROVIDE |
| | CALCULATIONS SHOWING THAT CONNECTORS |
| | (TOP AND BOTTOM) WILL RESIST THE LOADS |
| | TRANSFERED FROM THE FLOOR DIAPHRAGM. |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC |
| | 3-CLARIFY COL. SCHEDULE. P1 IS 6X8 POST. |
| | WHAT IS 4X10 W/ 2X10 NAILED TOGETHER? |
| | ALSO, USP PA66 IS NOT GOOD FOR A 6X8 |
| | POST. REVISE AS REQUIRED. |
| | 4-NEED RECORDED NOTICE OF COMMENCEMENT. |
| | 5-SPECIFY FIREBLOCKING AT TOP OF STAIRS. |
| | SEC. 2305.2.2 FBC 2001. |
| | NOTE: DRAW TOP & BOTTOM TRUSS CHORD TO |
| | SCALE TO CLARIFY DETAIL. |
| | 6-NEED SIGNED & SEALED SOIL TEST REPORT. |
| | 7-STORM SHUTTERS: |
| | A)DRAWINGS DON'T MATCH REPORT AND ARE |
| | NOT LEGIBLE. |
| | B)CHECK KEY PLAN AND INSTALLATION SCHED. |
| | WITH ACTUAL PLANS SUBMITTED. |
| | 8-PROVIDE PRODUCT APPROVAL FOR: |
| | A)ENTRY DOORS W/ LEGIBLE REPORT & DWGS. |
| | B)SINGLE HUNG WINDOWS FIRST PAGE OF |
| | REPORT DOESN'T MATCH THE REST. |
| | C)ARCHED WINDOWS. SEE SIZES SHOWN ON |
| | PLANS. |
| | 9-PROVIDE 2X STRUCTURAL BUCK DETAIL FOR |
| | ARCHED WINDOWS AS REQUIRED BY PRODUCT |
| | APPROVAL. NOTE DETAIL SUBMITTED IS NOT |
| | CORRECT. SEE ARCHED OPENINGS. THERE IS |
| | NOT FRAMED WALL. REVISE AS REQUIRED. |
| | 10-SHEET C1 WAS NOT CHANGED. |
| | 11-PROVIDE COMPLETE DETAILS & SPECS FOR |
| | FRAMED WALLS SHOWING HOW ARE SHEAR |
| | WALLS TRANSFERING THE LOADS. SEE SEC. |
| | 2313 FBC 2001. |