| Plan Review Notes For Permit 02060552 |
| Permit Number |
02060552 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-19 00:00:00 | PROVISO:MECHANICAL PERMIT 02060642 | | | | | | CONDENSATE SHALL DISCHARGE A MINIMUM OF | | | 12" AWAY FROM THE BUILDING STRUCTURE AS | | | PER 2001 FBC 1503.4.4. | | | | | | SMOKE DETECTORS SHALL BE INSTALLED IN | | | SUPPLY SYSTEMS WITH A DESIGN CAPACITY | | | GREATER THAN 2,000 CFM, IN THE SUPPLY | | | AIR DUCT. 2001 FBC(M) 606.2.1 | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | | WITH NOTIFICATION TO ALARM/STOBE OR AREA | | | SMOKE DETECTORS. 2001 FBC(M) 606.4.1 | | | | | | DEVELOPED DUCT LENGTH FOR THE DRYER | | | SHALL NOT EXCEED 25 FT FROM THE DRYER | | | LOCATION TO THE OUTLET TERMINAL. THIS | | | LENGTH SHALL BE REDUCED 5 FT FOR EVERY | | | 90 DEGREE BEND & 2 1/2 FT FOR EACH 45 | | | DEGREE BEND.4" MINIMUM DUCT SIZE. | | | 2001 FBC(M) 504.6 | | | | | | 2001 FBC(M) 402.2 - NATURAL VENTILATION | | | FOR OUTSIDE AIR REQUIRMENT. SHOW | | | COMPLIANCE FOR THE MINIMUM OPENABLE AREA | | | TO THE OUTDOORS. (4 PERCENT OF THE FLOOR | | | AREA BEING VENTILATED) OR TABLE 403.3 | | | FOR MECHANICAL VENTILATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|