Plan Review Notes
Plan Review Notes For Permit 02060543
Permit Number 02060543
Review Stop E
Sequence Number 1
Notes
Date Text
2002-06-19 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 AND RESUBMIT FOR REVIEW.
  
 1} THE RISER DIAGRAM SHOWS A 200A/2P
 DISCONNECT AND A 200 AMP PANEL,BUT THE
 PLANS ONLY SHOW A PANEL.PLEASE CLARIFY.
  
 2} THE WIRE SHOWN GOING TO THE 200 AMP
 PANEL IS LISTED AS #1,WHICH IS ONLY
 GOOD FOR 150 AMPS PER 310-15(B)(6).
 AND THE PANEL IS SHOWN AS MLO.PLEASE
 CLARIFY.
  
 3} THE DRAWING DOES NOT SHOW HOW THE
 BRANCH CIRCUITS ARE BEING REFED. PLEASE
 NOTE IF USING THE EXISTING PANEL AS A
 JUNCTION BOX IT MUST BE ACCESSIBLE PER
 370-29.
  
 4} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 5} PLEASE NOTE THAT THE A COUNTER
 RECEPTACLE IS REQUIRED NEXT TO THE
 REFER/ICE MAKER PER 210-52(C)(1),IF 1'.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392