Plan Review Notes
Plan Review Notes For Permit 02060519
Permit Number 02060519
Review Stop E
Sequence Number 1
Notes
Date Text
2002-09-11 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY
 CORRECTIONS TO THE PLANS AND RESUBMIT
 FOR REVIEW.
  
 1} PLEASE PROVIDE INFORMATION AS TO
 HOW THE PERMIT VALUATION WAS
 ESTABLISHED PER 104.6.5 CWPB
 AMMENDMENTS(ATTACHED).
  
 2} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 3} PLEASE INDICATE THE LOCATION OF THE
 SERVICE EQUIPMENT ON THE PLAN.
  
 4} INDICATE THE SIZE OF THE CONDUIT AND
 WIRE BETWEEN THE METER AND THE PANEL.
  
 5} PLEASE NOTE THE OCP FOR THE WATER
 HEATER MUST COMPLY WITH 422-11(E)(3).
  
 6} PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
 7} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 8} SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 IN THE VICINITY OF BEDROOMS AND CLOSE
 PROXIMITY OF STAIRWAYS. 2-5.2.1.3
 3'FT FROM BATHS/KITCHENS.2-5.2.1.6
  
 9} ALL LOW VOLTAGE TO BE INSTALLED MUST
 BE SHOWN ON DRAWING.
  
 10} ELECTRICAL PERMIT IS REQUIRED.
  
 11} PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.
 SHALL HAVE A TITLE BLOCK.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392