| Plan Review Notes For Permit 02060492 |
| Permit Number |
02060492 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-14 00:00:00 | 1) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO,DURING AND AFTER CONSTRUCTION. | | | | | | 2) FIRE HYDRANTS ARE TO BE SPACED | | | BETWEEN 300-500 FEET. | | | | | | 3) NO OBJECTS ARE TO BE PLACED TO | | | OBSTRUCT THE OPERATIONS OF THE FIRE | | | HYDRANTS. | | | | | | 4) DEAD-END ROADS GREATER THAN 150 FEET | | | IN LENGTH MUST HAVE APPROVED | | | TURN-AROUNDS AT LEAST 50 FEET OF | | | CENTERLINE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|