| 2002-06-12 00:00:00 | *******************DENIED*************** |
| | |
| | PLEASE PROVIDE THE FOLLOWING INFORMATION |
| | FOR REVIEW. |
| | |
| | 1.INDICATE LOCATIONS OF ANY NEW FIRE |
| | DAMPERS TO BE INSTALLED AS PER 2001 |
| | FBC(M) 607.6.THE FOLLOWING ARE A |
| | LIST OF PENETRATIONS IN QUESTION. |
| | CORRIDOR 549 - PLANS SHEET A-2.1 |
| | INDICATES 1HR. CONFERENCE RM 562 HR |
| | RATING.PLANS ARE UNCLEAR AS TO THE |
| | RATING OF MECHANICAL, ELECTRICAL & |
| | STORAGE ROOM.PLEASE CLARIFY. |
| | |
| | 2.PLEASE PROVIDE OUTSIDE AIR CALCS AS |
| | PER 2001 FBC(M) TABLE 403.3 OR |
| | ASHRAE 62-89. |
| | |
| | 3.AS PER 2001 FBC(M) 602.2.1 MATERIALS |
| | EXPOSED WITHIN PLENUMS SHALL BE NON- |
| | COMBUSTIBLE OR SHALL HAVE A FLAME |
| | SPREAD INDEX OF NOT MORE THAN 25 & |
| | A SMOKE-DEVELOPED INDEX OF NOT MORE |
| | THAN 50 WHEN TESTED IN ACCORDANCE |
| | WITH ASTM E 84. |
| | |
| | 4.PRESSURE DIFFIERENTIALS ACROSS |
| | CLOSED DOORS SHALL BE LIMITED TO |
| | .001 IN WC OR LESS.PROVIDE AIR |
| | TRANSFER PATHWAYS OR AIR DUCT PATH- |
| | WAYS FOR COMPLIANCE. 2001 FBC(M) |
| | 601.4 |
| | |
| | 5.INDICATE DUCT SMOKE DETECTORS ON |
| | PLAN - NEW OR EXISTING. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT 659-8096 |
| | EXT. 8388. |