Plan Review Notes
Plan Review Notes For Permit 02060458
Permit Number 02060458
Review Stop FS
Sequence Number 2
Notes
Date Text
2002-09-12 00:00:001) ALL FIRE DEPARTMENT CONNECTIONS ARE
 TO FACE THE CORRECT DIRECTION. ALL FIRE
 PROTECTION DEVICES ARE TO BE PROVIDED
 WITH 7 FEET 6 INCHES OF CLEARANCE.
 ALL FIRE DEPARTMENT CONNECTIONS ARE TO
 BE NO FARTHER THAN 150 FEET FROM A FIRE
 HYDRANT.
  
 2) SPARE SPRINKLER HEADS AND WRENCHES
 ARE TO BE PROVIDED FOR EACH BUILDING.
  
 3) WET FIRE HYDRANTS ARE TO BE PROVIDED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 4) ALL BACKFLOW DEVICES ARE TO BE
 EQUIPPED WITH FLOW AND TAMPER SWITCHES.
  
 5) CVPC ARE NOT PERMITTED FOR ORDINARY
 HAZARD OCCUPANCIES.
  
 6) ALL INSTALLATIONS ARE SUBJECT TO
 FIELD INSPECTIONS BY FIRE RESCUE.
  
 7)