| Plan Review Notes For Permit 02060458 |
| Permit Number |
02060458 |
|
| Review Stop |
FS |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-09-12 00:00:00 | 1) ALL FIRE DEPARTMENT CONNECTIONS ARE | | | TO FACE THE CORRECT DIRECTION. ALL FIRE | | | PROTECTION DEVICES ARE TO BE PROVIDED | | | WITH 7 FEET 6 INCHES OF CLEARANCE. | | | ALL FIRE DEPARTMENT CONNECTIONS ARE TO | | | BE NO FARTHER THAN 150 FEET FROM A FIRE | | | HYDRANT. | | | | | | 2) SPARE SPRINKLER HEADS AND WRENCHES | | | ARE TO BE PROVIDED FOR EACH BUILDING. | | | | | | 3) WET FIRE HYDRANTS ARE TO BE PROVIDED | | | PRIOR TO, DURING AND AFTER CONSTRUCTION. | | | | | | 4) ALL BACKFLOW DEVICES ARE TO BE | | | EQUIPPED WITH FLOW AND TAMPER SWITCHES. | | | | | | 5) CVPC ARE NOT PERMITTED FOR ORDINARY | | | HAZARD OCCUPANCIES. | | | | | | 6) ALL INSTALLATIONS ARE SUBJECT TO | | | FIELD INSPECTIONS BY FIRE RESCUE. | | | | | | 7) |
|