| Notes |
| Date |
Text |
| 2002-06-19 00:00:00 | 1) PLEASE INDICATE LOCATIONS OF FDC'S | | | FOR RETAIL SPACES B,C,AND D. | | | | | | 2) POST INDICATOR VALVES ARE TO BE | | | LOCATED NO FARTHER THAN 40 FEET FROM | | | THE BUILDINGS THEY CONTROL. | | | | | | 3) ENGINEERING INFORMATION ON PLANS | | | NOT NEEDED. | | | | | | 4) PLEASE PROVIDE A COMPLETE SITE PLAN | | | FOR THE COMPLEX INDICATING FIRE HYDRANTS | | | FIRE DEPARTMENT CONNECTIONS AND POST | | | INDICATOR VALVE LOCATIONS. | | | | | | 5) ALL OS&Y VALVES ARE TO BE SUPERVISED. | | | | | | 6) SOME BACKFLOW DEVICE DETAILS SHOW | | | NO FDC INFORMATION. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|