2002-06-19 00:00:001) PLEASE INDICATE LOCATIONS OF FDC'S
 FOR RETAIL SPACES B,C,AND D.
  
 2) POST INDICATOR VALVES ARE TO BE
 LOCATED NO FARTHER THAN 40 FEET FROM
 THE BUILDINGS THEY CONTROL.
  
 3) ENGINEERING INFORMATION ON PLANS
 NOT NEEDED.
  
 4) PLEASE PROVIDE A COMPLETE SITE PLAN
 FOR THE COMPLEX INDICATING FIRE HYDRANTS
 FIRE DEPARTMENT CONNECTIONS AND POST
 INDICATOR VALVE LOCATIONS.
  
 5) ALL OS&Y VALVES ARE TO BE SUPERVISED.
  
 6) SOME BACKFLOW DEVICE DETAILS SHOW
 NO FDC INFORMATION.
  