| Plan Review Notes For Permit 02060449 |
| Permit Number |
02060449 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-08-01 00:00:00 | ************** UNSAT **************** | | | | | | REVISION SUBMITTED FOR NEW TEMPORARY | | | ELECTRICAL SERVICE TO FEED CAROUSEL. | | | | | | 1)NOTE: PLEASE CORRELATE CONDUIT SIZES | | | THAT ARE NOTED. PLEASE NOTE #1 SAYS | | | 4" CONDUITS AND NOTES #6 AND #9 SHOW | | | 2" CONDUITS?? | | | | | | 2)NOTE:PLEASE NOTE;NOTE #6 SHOWS AN | | | EQUIPMENT GROUNDING CONDUCTOR FROM | | | TRANSFORMER/FPL TO METER. PLEASE NOTE | | | THAT THIS IS PARALLELING THE NEUTRAL. | | | 250-24 | | | | | | 3)NOTE: PLEASE NOTE THAT CONTRACTOR | | | NEEDS TO SUBMIT PERMIT APPLICATION FOR | | | TEMP POWER/FEED. | | | | | | 4)NOTE: PLEASE SHOW LOCATION OF NEW | | | DISC ON PLANS. PLEASE NOTE ONLY PULL | | | BOX IS SHOWN? | | | | | | 5)NOTE: PLEASE PROVIDE INFORMATION FOR | | | DISTANCE FROM TRANSFORMER TO PANEL. | | | / PROVIDE VOLTAGE DROP CALCUALTIONS. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|