Plan Review Notes
Plan Review Notes For Permit 02060449
Permit Number 02060449
Review Stop E
Sequence Number 2
Notes
Date Text
2002-08-01 00:00:00************** UNSAT ****************
  
 REVISION SUBMITTED FOR NEW TEMPORARY
 ELECTRICAL SERVICE TO FEED CAROUSEL.
  
 1)NOTE: PLEASE CORRELATE CONDUIT SIZES
 THAT ARE NOTED. PLEASE NOTE #1 SAYS
 4" CONDUITS AND NOTES #6 AND #9 SHOW
 2" CONDUITS??
  
 2)NOTE:PLEASE NOTE;NOTE #6 SHOWS AN
 EQUIPMENT GROUNDING CONDUCTOR FROM
 TRANSFORMER/FPL TO METER. PLEASE NOTE
 THAT THIS IS PARALLELING THE NEUTRAL.
 250-24
  
 3)NOTE: PLEASE NOTE THAT CONTRACTOR
 NEEDS TO SUBMIT PERMIT APPLICATION FOR
 TEMP POWER/FEED.
  
 4)NOTE: PLEASE SHOW LOCATION OF NEW
 DISC ON PLANS. PLEASE NOTE ONLY PULL
 BOX IS SHOWN?
  
 5)NOTE: PLEASE PROVIDE INFORMATION FOR
 DISTANCE FROM TRANSFORMER TO PANEL.
 / PROVIDE VOLTAGE DROP CALCUALTIONS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372