| 2002-06-28 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 CHAPTER 11 |
| | FBC-2001 PLUMBING |
| | |
| | 1) A DRINKING FOUNTAIN AND A SERVICE |
| | SINK ARE REQUIRED PER TABLE 403.1 |
| | SEE 11-4.15 AND 11-4.1.3(10) PROVIDE |
| | DETAILS FOR DRINKING FOUNTAIN. |
| | 2) SHT A3 DETAIL #4, SINK TO COMPLY WITH |
| | 11-4.24 PROVIDE DETAILS. |
| | 3) SHT A3 DETAIL #3, URNAL SHALL COMPLY |
| | WITH 11-4.18.2, MAX HEIGHT 17". SHOW ON |
| | DETAIL. |
| | 4) SHT P-1 KEYNOTE (2) 2-1/2" AND SMALL- |
| | ER PIPE SHALL BE RUN AT 1/4" PER FOOT |
| | PER TABLE 704.1. PLEASE CHANGE NOTE. |
| | 5) SHTS P-1/P-2 WATER HEATER DETAIL, PER |
| | 504.7.1 THE RELIEF (T/P) DISCHARGE LINE |
| | SHALL NOT HAVE ANY TRAPPED SECTIONS AND |
| | SHALL HAVE A VISIBLE AIR GAP OR AIR GAP |
| | FITTING LOCATED IN THE SAME ROOM AS THE |
| | WATER HEATER. PROVIDE DETAILS. |
| | 6) SHT P-1 WATER ISOMETRIC SHOWS TWO 1/2 |
| | INCH COLD LINES RUN TO A SINK NOT SHOWN |
| | ON THE FLOOR PLAN. PLEASE CLAIRFY. |
| | 7) SHT P-1 WATER ISOMETRIC, AIR CHAMBERS |
| | ARE NOT APPROVED. WATER HAMMERS ARE RE- |
| | QUIRED FOR ALL QUICK CLOSING VALVES PER |
| | 604.9. (SEE SHT P-2 PLUMBING SYMBOLS & |
| | ABBREVIATIONS) |
| | 8) SHT P-1 SANITARY ISOMETRIC DOES NOT |
| | REFLECT THE FLOOR PLAN. FLOOR DRAINS |
| | PRIOR TO BACK TO BACK URNAL AND WATER |
| | CLOSET ARE NOT SHOWN ON SANT. ISO. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |