| 2004-12-22 00:00:00 | ****CORRECTIONS**** |
| | VARIOUS SUBMITTALS; CLARIFICATION |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)THE FAX RECEIVED IN REGARDS TO THE |
| | HORTON AUTOMATIC DOORS, C101, C151 AND |
| | A123, IS ACCEPTABLE.PLEASE SUBMIT |
| | ORIGINALS, SIGNED & SEALED. |
| | |
| | 2.)THE LETTER FROM PAUL KING, PE |
| | DATED |
| | NOVEMBER 11, 2004 RE: WINDOW PRESSURES |
| | STATING THAT 102B AND B102C (OVERHEAD |
| | DOORS) SHALL BE DESIGNED TO ACCOMODATE |
| | ZONE 4 PRESSURES IS NOT CLEAR.ARE |
| | THEY |
| | ALL LOCATED IN ZONE 4 OR ARE YOU |
| | REVISING THE ZONE 5 PRESSURES STATED ON |
| | SHEET S2.19? |
| | |
| | 3.)THE LETTER FROM PAUL KING DOES NOT |
| | ADDRESS THE |
| | SLIDING GLASS DOORS OR THE NOAS |
| | SUBMITTED (02-0712.03, 02-0712.01). |
| | |
| | 4.)REGARDING NOA 02-0712.03(DP+-70) |
| | FOR DOORS A131, A122A, B1014, AND |
| | NOA02-0712.01 FOR DOOR A131A ARE ANY OF |
| | THESE DOORS LOCATED IN ZONE 5, AND IS |
| | WATER INFILTRATION REQUIRED? |
| | |
| | 5.)ENGINEERING FROM AL-FAROOQ FOR THE |
| | SLIDING GLASS DOORS (SHEET SD-03-44) |
| | PROVIDE DESIGN PRESSURES. IT IS NOT |
| | CLEAR WHY THEY ARE LOWER THAN THE TEST |
| | REPORT.SINCE THE DOR |
| | SPECIFIES DESIGN PRESSURES FOR THE |
| | BUILDING (SHEET S2.19) THEY APPEAR TO |
| | BE |
| | DESIGN PRESSURE LIMITATIONS FOR THE |
| | SLIDING GLASS DOORS.THEY ARE |
| | NONCOMPLIANT FOR ZONE 5 (REQUIREMENT OF |
| | -77.4, -75.05, -73.2).IF ZONE 5 IS |
| | WITHIN 15' OF A CORNER AS STATED ON |
| | S2.19, IT APPEARS THAT ALL OF THE |
| | SLIDING GLASS DOORS, WITH THE EXCEPTION |
| | OF SOME LOCATED AT THE POOL ENCLOSURE, |
| | ARE LOCATED IN ZONE |
| | 5.PLEASE SUBMIT NEW TEST REPORTS. |