| 2003-07-25 00:00:00 | PASSED/PROVISO |
| | |
| | SHT P-103 LOCKER ROOM SANITARY/VENT |
| | RISER, HORIZONTAL DRY VENT NOT APPROVED. |
| | WATER CLOSET SHALL TIE IN ON THE VERTIC- |
| | AL RISE. SECTION 905.3- REVISION REQD. |
| | |
| | SHT P-301 VALVES REQUIRED ON WATER RISER |
| | SECTION 606.1(4) |
| | SHT P-407 VALVES REQUIRED ON WATER RISER |
| | SECTION 606.1(4) |
| | |
| | SHT P-409 VENTS AND LAV ARM NOT SHOWN ON |
| | RISER "B" REVISION REQUIRED. |
| | |
| | |
| | --GAS PERMIT APPLICATION REQUIREMENTS--- |
| | WELDER'S CERTIFICATION, PICTURE I.D. AND |
| | WELDING PROCEDURE REQUIRED PRIOR TO |
| | ISSUING OF GAS PERMIT. |
| | WELDING INSPECTIONS REQUIRED: TACK-UP, |
| | ROOT PASS, FILLER PASS. COVER PASS CAN |
| | BE INSPECTED AT TIME OF ROUGH INSPECTION |
| | SHUT OFF VALVES UPSTREAM OF REGULATORS |
| | REQUIRED AT EACH GAS FIXTURE. UNION RE- |
| | QUIRED DOWNSTREAM OF REGULATOR. PIPE |
| | SIZES TO BE CORRECTED AT 750,000 BTU |
| | HEATERS. 2" REQUIRED. PIPE SIZES NOT |
| | SHOWN ADJACENT TO METER. SUBMIT A REVIS- |
| | ED GAS RISER WITH THESE CORRECTIONS WITH |
| | GAS APPLICATION. |
| | MANUFACTURE CUT SHEET REQUIRED FOR THE |
| | REGULATORS, DISHWASHER, UDS EQUIPMENT. |
| | CUT SHEETS FOR GAS APPLIANCES SHALL SHOW |
| | A LISTING BY AN APPROVED AGENCY AND BTU |
| | LOAD FOR EACH APPLIANCE. (LOCHIVAR UNITS |
| | DO NOT SHOW A LISTING) |
| | |