| Date |
Text |
| 2003-03-21 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 FUEL GAS |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 FHA-98 DESIGN MANUAL |
| | |
| | 1) MOST OF THE FOLLOWING COMMENTS WERE |
| | FROM THE PREVIOUS PLAN REVIEW AND WERE |
| | NOT ADDRESSED. |
| | 2) PLANS SHALL BE ROUTED TO THE PALM |
| | BEACH HEALTH UNIT. |
| | 3) GREASE TRAP SHALL BE SIZED BY UTILITY |
| | DEPT. CONTACT R. COMPO (561) 837-4074. |
| | 4) SHT A-2.31 SUBMIT CALCULATIONS FOR |
| | PRIMARY AND SECONDARY ROOF DRAINS. IN- |
| | CLUDE 1/2 AREA OF ALL VERTICAL WALLS, |
| | AND AREA OF ROOFS DRAINING ON TO ROOF |
| | FROM ABOVE. |
| | 5) SUBMIT A HORIZONTAL STORM BLDG DRAIN. |
| | SHOW ALL RISERS AS THEY TIE INTO STORM |
| | DRAIN AS SHOW SQUARE FOOTAGE AS IT ACCU- |
| | MULATES IN SYSTEM. |
| | 6) SHTS A-2.41, A-2.42, & A-2.43, NO |
| | MEASUREMENTS FOR BACKING SHOWN ON PLANS. |
| | SPECIFICATION "A" OR "B" ARE NOT SHOWN |
| | AS REQUIRED IN REQ. #7. W/C OPENING NOT |
| | SHOWN AS REQUESTED. |
| | 7) SHT A-8.11 TURNING CIRCLE NOT SHOWN |
| | IN EACH TOILET ROOM AS REQUIRED. |
| | 8) SHT A-8.13 ELEVATIONS 8B, 8C, & 8D DO |
| | NOT MATCH INDICATOR ON DETAIL #1 SHT. |
| | A-2.41 |
| | 9) SHT P-102 WATER HEATER "A" DETAIL, |
| | COMBUSTION AIR INTAKE SHALL BE SIZED AND |
| | INSTALLED PER MANUF. INSTALL. INSTRUCTS. |
| | PROVIDE INFORMATION FOR REVIEW. |
| | 10) SHTS P-103 & P-404 WATER RISERS, |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURES IN AN EFFECTIVE RANGE, |
| | NOT IN CEILING. PER PDI-WH 201 AND MANUF |
| | INSTALL. INSTRUCTIONS. |
| | 11) SHTS P-103, P-202, & P-404, VENTS |
| | ARE REQUIRED FOR SHOWERS IN MENS & WO- |
| | MENS LOCKER ROOMS. |
| | 12) SHT P-201 SANITARY DRAINAGE PIPE |
| | (BURIED) DOES NOT MATCH LEDGEND ON SHT |
| | P-101. (ALSO SHT P-202) |
| | 13) SHT P-202 CLEAN OUTS REQUIRED IN |
| | SANITARY BLDG. DRAIN. MAX. 100'. |
| | 14) SUBMIT A SANITARY BLDG DRAIN. SHOW |
| | PIPE SIZES, CLEANOUTS, RISERS, AND SHOW |
| | FIXTURE UNITS AS THEY ACCUMULATE IN THE |
| | BLDG DRAIN. |
| | 15) SHT P-202 ITEM P-145 FILTER TO BE |
| | NSF APPROVED. PROVIDE MANUF. INFORMATION |
| | 16) SHTS P-202/P-203, ITEMS P-125, AND |
| | P-124, FUNNEL DRAINS NOT APPROVED. ALL |
| | INDIRECT WASTE SHALL DRAIN INTO FLOOR |
| | SINKS. SEC 802.3 |
| | 17) SHT P-207 STACK B/19 NOT FOUND. |
| | PLEASE CLAIRFY. ROOM C220 |
| | 18) SHT P-207 STACK KS/9 IN MIDDLE OF |
| | ROOM? NO WATER TO KITCHEN SINK. RM C220 |
| | 19) SHTS P-216 & P-218, SIZE WATER MAINS |
| | OVERHEAD IN CORRIDOR. |
| | 20) SHT P-301 SHOW PIPE SIZES FOR RISER |
| | "A". |
| | 21) SHT P-401 SHOW PIPE SIZES FOR WATER |
| | MAINS IN KITCHEN CEILING. |
| | 22) SHT P-405 BTU LOAD OF GAS APPLIANCES |
| | SHOWS 5,189,000 ON PLANS BUT ONLY ADDS |
| | UP TO 4,266,000. PLEASE CLAIRFY. |
| | 23) SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR PER FBC-2001 FUEL GAS CODE SECTION |
| | 304. SUBMIT MANUF. INFO. FOR COMBUSTION |
| | AIR DIRECT VENT. |
| | 24) SUBMIT MANUF. SHEET FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, AND THE FBC-2001 FUEL |
| | GAS CODE SEC 402.2 |
| | 25) EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | 26) SHT P-402 SANT. RISERS B/4, B/5, B/6 |
| | B/8, B/9, & KS/2 - VENT SHALL NOT TIE |
| | BACK INTO WASTE STACK AS SHOWN. |
| | 27) SHTS P-402, & P-403 ALL VENT STACKS |
| | SHALL BE WASHED AT THE BASE. START ALL |
| | VENT STACKS FROM THE LOWEST FIXTURE |
| | GROUP. |
| | 28) SHT P-403 RISERS B/15, B/16, & B/18 |
| | VENT SHALL NOT TIE BACK INTO WASTE STACK |
| | AS SHOWN. |
| | |
| | WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 OR805-6721 |
| | FAX 653-2692 |
| | BUILDING PLAN REVIEW |