| Date |
Text |
| 2003-04-11 00:00:00 | 1.PLAN SHEET M-102 NOTE #4, "SEE |
| | M-200" THIS SHEET WAS NOT SUBMITTED. |
| | NOTE #6 "SEE DIVISION 16 SERIES DWG", |
| | PLEASE CLARIFY. |
| | |
| | 2.PLAN SHEET M-101, ATRIUM SMOKE |
| | CONTROL - CODE SECTION 403.6.6.1, SHOULD |
| | THIS READ 414.4.2. |
| | |
| | 3.PLAN SHEET M-202, PLAN NOTE #4 |
| | "RANGE HOOD BY OTHERS" - SEPARATE PLANS |
| | AND PERMITS REQUIRED FOR HOOD, FIRE |
| | SUPPRESSION AND WALK-IN COOLERS. |
| | |
| | 4.PLAN SHEET M-203, HOOD CONNECTION |
| | TRANSITION DUCTWORK COMMENTS 1,2,& 11, |
| | INDICATE GREASE DUCT CLEARANCE TO |
| | COMBUSTIBLES, WILL DUCT BE IN A SHAFT, |
| | OR WILL FIREWRAP BE USED? |
| | |
| | 5.M-203, DUCT PENETRATIONS INTO AHU |
| | ROOM A135 NO FIRE DAMPERS INDICATED. |
| | |
| | 6.MULTIPLE FLOORS HAVE "STORAGE & |
| | ELECTRICAL" ROOMS THAT HAVE A 1 HOUR |
| | FIRE RESISTANCE RATING.THE MECHANICAL |
| | PLANS CALL FOR UNDERCUT DOOR FOR AIR |
| | MAKE UP.PLEASE CLARIFY HOW THE RATING |
| | IS MET WITH THE DOOR UNDERCUT. |
| | |
| | 7.PLEASE NOTE, DEVELOPED LENGTH FOR |
| | DRYER DUCTS SHALL NOT EXCEED 25 FT. WITH |
| | A 5 FT REDUCTION FOR EACH 90 DEGREE |
| | RADIUS AND A 2 1/2 FT. REDUCTION FOR |
| | EACH 45 DEGREE RAD. |
| | |
| | PROVIDE TEST CRITERIA FOR THE SMOKE |
| | CONTROL. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |