| Date |
Text |
| 2003-04-24 00:00:00 | 1) AL DINING ROOM A128,A128B, DISPLAYS |
| | ONLY ONE EXIT SIGN. |
| | |
| | 2) IS THE DOOR SWING SHOWN IN DINING |
| | ROOM AREA A, SWINGING IN THE RIGHT |
| | DIRECTION. |
| | |
| | 3) EXIT SIGN IN MULTI-USE FOYER C156 |
| | LEADS WHERE. |
| | |
| | 4) VERANDA'S REQUIRED TO BE FIRE |
| | SPRINKLER PROTECTED IF COMBUSTIBLE |
| | CONSTRUCTION OR COMBUSTIBLES ARE |
| | HANDLED OR STORED. |
| | |
| | 5) CORRIDOR A301 NEEDS EXIT SIGN AT |
| | HALLWAY INTERSECTION. |
| | |
| | 6) PLEASE INDICATE TRAVEL DISTANCES |
| | ON FLOORS 4,5,AND 6. |
| | |
| | 7) PLEASE INDICATE WHICH ELEVATORS ARE |
| | STRETCHER ACCESSIBLE. |
| | |
| | 8) PLEASE PROVIDE PRODUCT APPROVALS FOR |
| | WON-DOORS. |
| | |
| | 9) WHAT PREVENTS PERSONS FROM SLIPPING |
| | ON THE MARBLE TREADS ON THE GRAND STAIR. |
| | |
| | 10) PLEASE DISPLAY THE RESISTANT TO THE |
| | PASSAGE OF A 4" SPHERE ON HANDRAILS. |
| | |
| | 11) PLEASE DISPLAY AISLES IN DINING |
| | ROOMS 177A AND 177B. |
| | |
| | 12) THE LOCATION OF FIREFIGHTERS SMOKE |
| | CONTROL ATRIUM PANEL SHOULD BE LOCATED |
| | WHERE ALL OTHER LS SYSTEM PANELS ARE |
| | LOCATED. |
| | |
| | 13) PLEASE PROVIDE TESTING REQUIREMENTS |
| | AND A SEQUENCE OF OPERATION FOR ATRIUM |
| | SMOKE CONTROL. |
| | |
| | 14) FP SCHEDULE AND NOTES BELOW IT DO |
| | NOT CORRESPOND. |
| | |
| | 15) PLEASE EXPLAIN WHY POOL AREA IS NOT |
| | FIRE SPRINKLER PROTECTED. |
| | |
| | 16) HOW ARE TWO STANDPIPES SHOWN ON |
| | PLANS 4-6TH FLOORS ABLE TO COVER ALL |
| | AREAS OF THE BUILDING. |
| | |
| | 17) PLEASE INDICATE HOW SECURITY |
| | FEATURES INSTALLED ON EXIT DOORS |
| | WILL EFFECT EXITING. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |
| | 835-2910 |