| Plan Review Notes For Permit 02060381 |
| Permit Number |
02060381 |
|
| Review Stop |
P |
| Sequence Number |
13 |
|
| Notes |
| Date |
Text |
| 2004-01-08 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) SHTS P207, P208, P217, & P218 ALL | | | SHOW 2" CONDENSATE RISER WITH A 2" HUB | | | DRAIN, BUT SHOW 3" PIPED TO THE HUB | | | DRAIN. PLEASE CLAIRFY. | | | 2) SHT P-402 SANITARY RISERS B/9 & B/25 | | | JANITOR SINK HAS BEEN ADDED TO RISERS. | | | PER SECTION 909.1, ONLY THE FIXTURES | | | WITHIN THE BATHROOM GROUP SHALL CONNECT | | | TO THE WET-VENTED HORIZONTAL BRANCH | | | DRAIN. ANY ADDITIONAL FIXTURES SHALL | | | DISCHARGE DOWNSTREAM OF THE WET VENT. | | | 3) SHT P-407 SANITARY RISER B/50 TRAP | | | REQUIRED ON FIXTURE T-1 (TUB) 1002.1 | | | 4) SHT P-407WATER RISERS 'A' & 'B' NO | | | CHANGES WERE NOTED BUT RISERS WERE | | | CLOUDED. WATER RISER 'A' REQUIRES FULL | | | OPEN VALVES PER 606.1(4) AS INDICATED ON | | | STAMPED SET OF PLANS. ALSO WASH MACHINE | | | REQUIRES WATER HAMMER ARRESTORS NEAR THE | | | FIXTURE. 604.9 | | | 5) INFORMATIONAL - SHTS P-103 AND P-410 | | | REQUIRE REVISIONS PER STAMPED SET OF | | | PLANS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|