| 2002-07-03 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 FUEL GAS |
| | FBC-2001 SECTION 424 POOLS |
| | |
| | 1) PLANS SHALL BE ROUTED TO THE PALM |
| | BEACH HEALTH UNIT, DIVISION OF ENVIRON- |
| | MENTAL HEALTH, 901 EVERNIA WPB (561) 355 |
| | 3018 FOR KITCHEN AND POOL. |
| | 2) GREASE TRAP SHALL BE SIZED BY UTILITY |
| | DEPT. PLEASE CONTACT RODNEY COMPO, |
| | ENVIRONMENTAL MANAGER, (561) 837-4074. |
| | 3) PLEASE PROVIDE CALCULATIONS FOR MINI- |
| | MUM FACILITIES. USE TABEL 403.1. |
| | 4) SHTS A-201B - A-2.21B TOILET STALLS |
| | SHALL HAVE A LAV. SEE FIG 30E IN CHAPTER |
| | 11 FBC-2001. |
| | 5) SHT A-2.31 PLEASE SUBMIT CALCULATIONS |
| | FOR PRIMARY AND SECONDARY ROOF DRAINS |
| | PER SECTIONS 1106 & 1107. INCLUDE 1/2 |
| | AREA OF ALL VERTICAL WALLS AND AREA OF |
| | ROOFS DRAINING ON TO ROOF FROM ABOVE. |
| | SHOW LOCATION OF SECONDARY DRAINS. |
| | 6) PLEASE SUBMIT A STORM RISER DIAGRAM. |
| | SHOW ALL RISERS WITH TOTAL SQ FT OF EACH |
| | RISER AND SHOW TOTAL SQ FT AS IT ACCUMU- |
| | LATES IN STORM DRAIN. |
| | 7) SHTS A-2.41, A-2.42, & A-2.43 ALL |
| | RESIDENTIAL UNITS SHALL COMPLY WITH FHA- |
| | AMEND 98 DESIGN MANUAL. ALL REQUIREMENTS |
| | #'S 1 THRU 7 SHALL BE MET, AND SPECIFI- |
| | CATION "A" OR "B" SHALL BE INDICATED ON |
| | PLANS FOR BATHROOMS. PLEASE SHOW CLEAR |
| | FLOOR SPACE AND INDICATE OPENING SIZE |
| | FOR EACH WATER CLOSET. |
| | 8) SHT A-8.11 DETAILS #1,2,3,4,5,6,7. |
| | PLEASE SHOW CLEAR FLOOR SPACE FOR ALL |
| | HDCP FIXTURES. SHOW TURNING RADIUS IN |
| | EACH TOILET ROOM. DOORS SHALL NOT SWING |
| | INTO THE CLEAR FLOOR SPACE OF ANY FIXT- |
| | URE OR THE UNOBSTRUCTED TURNING RADIUS |
| | FOR ANY FIXTURE. |
| | 9) SHT A-8.12 DETAIL #3 SHOW CONTROL |
| | HEIGHT FOR SHOWER. 11-4.21.5 |
| | 10) SHT P-101 PLUMBING NOTES #2 CODE IN |
| | EFFECT IS FBC-2001 PLUMBING NOT SPC. |
| | PLEASE CHANGE REFERENCE. |
| | 11) SHT P-101 PLUMBING NOTES #3B - PER |
| | MANUF. INSTRUCTIONS, AIR TESTS ON PVC |
| | PIPE AND FITTINGS ARE NOT APPROVED. |
| | PLEASE CHANGE NOTE. |
| | 12) SHT P-101 PLUMBING NOTES #5 - AIR |
| | CHAMBERS ARE NOT APPROVED. PLEASE DE- |
| | LETE REFERENCE. |
| | 13) SHT P-102 WATER HEATER "A" DETAIL, |
| | COMBUSTION AIR INTAKE SHALL BE SIZED AND |
| | INSTALLED PER MANUFACTURE INSTALLATION |
| | INSTRUCTIONS. PLEASE PROVIDE INFORMATION |
| | 14) SHT P-102 GREASE TRAP DETAIL. TWO |
| | WAY CLEAN OUTS REQUIRED ON BOTH SIDES OF |
| | THE GREASE TRAP. SEE ATTACHED SHEET FOR |
| | WPB APPROVED GREASE TRAP DETAIL. |
| | 15) SHT P-201 SANITARY DRAINAGE PIPE |
| | (BURIED) DOES NOT MATCH LEDGEND ON SHT |
| | P-101. PLEASE CLAIRFY. PLEASE SHOW DIFF- |
| | ERENCE BETWEEN BURIED PIPE & PIPE ABOVE |
| | CEILING. (ALSO ON SHT P-202) |
| | 16) SHT P-202 THERE ARE UNVENTED WATER |
| | CLOSETS, CLEAN OUTS REQUIRED (MINIMUM |
| | 100' BETWEEN CLEAN OUTS 708.3.1), UNVEN- |
| | TED FIXTURES, TWO SANT DRAIN LINES TO |
| | THE SAME WATER CLOSET. |
| | 17) SHT P-202 ITEM P-145 FILTER TO BE |
| | NSF APPROVED. PROVIDE MANUF INFO. |
| | 18) SHTS P-202/P-203 ITEMS P145B, P125, |
| | & P142 FUNNEL DRAINS NOT APPROVED. ALL |
| | INDIRECT WASTE SHALL DRAIN TO A FLOOR |
| | SINK. 802.3 |
| | 19) SHT P-205 STORM DRAIN NOT SIZED FOR |
| | LINE THAT EXITS AT -48" ELEVATION. |
| | 20) SHTS P-207, P-210, P-211, P-212, |
| | P-213, P-214, P-215, P-216, P-217, AND |
| | P-218. VARIOUS UNITS SHOW WATER LINES |
| | RUNNING TO RANGE/OVEN AND NOT TO KITCHEN |
| | SINK. SOME UNITS SHOW NO WATER TO KIT. |
| | SINKS. SOME UNITS SHOW WATER IN WALL |
| | ON THE OTHER SIDE OF ROOM FROM THE FIX- |
| | TURES IN BATHROOMS. PLEASE CHECK UNITS |
| | FOR THESE DISCREPANCIES. |
| | 21) SHTS P-212, P-216, & P-217 PLEASE |
| | SHOW SIZE FOR WATER PIPES RUNNING IN |
| | CEILING ABOVE CORRIDOR. |
| | 22) SHT P-301 BATHROOM PLAN, PLEASE SHOW |
| | CLEAR FLOOR SPACE FOR FIXTURES. |
| | 23) SHTS P-302, & P-401, ALL INDIRECT |
| | WASTE SHALL DRAIN INTO A FLOOR SINK. |
| | FUNNEL FLOOR DRAINS NOT APPROVED. 802.3 |
| | 24) SHTS P-302 & P-401 DISH WASH MACHINE |
| | SHALL DRAIN TO SANITARY NOT GREASE WASTE |
| | UTILITY ORD. |
| | 25) SHT P-401 DOMESTIC WATER RISER DIAG. |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR FIXTURE IN AN "EFFECTIVE RANGE" NOT |
| | AT TOP OF DROP AS SHOWN. WH-PDI 201 & |
| | MANUFACTURE INSTALL. INSTRUCTIONS. ALSO |
| | SHOW PIPE SIZES FOR KITCHEN MAINS. |
| | 26) SEPARATE PERMIT REQUIRED FOR GAS. |
| | SEE INFORMATION REQUIRED FOR GAS PERMIT |
| | APPLICATION BELOW. |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2001 |
| | FUEL GAS CODE. |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | C. TYPE OF GAS, (LP OR NATURAL) |
| | D. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | FBC-2001 FUEL GAS CODE SECS.401.8 THRU |
| | 402.5.2 & TABLES 402(1) THRU 402(34). |
| | E. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2001 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES (A)(3). |
| | F. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2001 FUEL |
| | GAS CODE. SEC 304. PLEASE SUBMIT MANUF. |
| | INFORMATION FOR COMBUSTION AIR DIRECT |
| | VENT. |
| | G. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2001 FUEL GAS SEC. 402.2. IF |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE FBC- |
| | 2001 FUEL GAS CODE SEDC 402.2. |
| | I. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | J. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND |
| | APPURTENANCES PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 3-2.2.7(H). |
| | K. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. |
| | 27) SUPPLY A SANITARY RISER DIAGRAM FOR |
| | THE BLDG DRAIN. SHOW ALL RISER CONNECT- |
| | IONS WITH FIXTURE UNIT LOAD FOR EACH |
| | RISER AND SHOW FIXTURE UNITS AS THEY |
| | ACCUMULATE IN THE SYSTEM TO VERIFY PIPE |
| | SIZE OF BLDG DRAIN. SHOW HOW ALL VENT |
| | LINES TIE INTO BLDG DRAIN. |
| | 28) P-402 RISERS B/4, B/5, B/6, B/9, & |
| | KS/2 VENT SHALL NOT TIE BACK INTO WASTE |
| | AS SHOWN. |
| | 29) SHTS P-402 & P-403 ALL VENT STACKS |
| | SHALL BE WASHED AT THE BASE. START ALL |
| | VENT STACKS FROM THE LOWEST FIXTURE |
| | GROUP. |
| | 30) SHT P-403 RISER B/16 2N FLOOR T-2 |
| | NOT VENTED. |
| | 31) SHT P-403 RISER B/15 W/C FOR 2ND |
| | FLOOR NOT VENTED. |
| | 32) SHT P-403 RISERS B/15, B/16, B/18 |
| | VENTS SHALL NO TIE BACK INTO WASTE STACK |
| | AS SHOWN. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 659-8096 EXT 8377 |