| 2002-07-09 00:00:00 | DENIED: |
| | 1. NO FIRE DAMPERS ARE SHOWN AT RATED |
| | WALLS. 2001 FBC(M) 607.6 THE SPECIFIC |
| | LOCATION AND INSTALLATION DETAILS OF |
| | EACH FIRE DOOR, FIRE DAMPER, CEILING |
| | DAMPER AND SMOKE DAMPER SHALL BE SHOWN |
| | AND PROPERLY INDENTIFIED ON THE |
| | BUILDING PLANS BY THE DESIGNER. |
| | |
| | 2. PROVIDE SHAFT DETAILS FOR EXHAUST |
| | RISERS. |
| | |
| | 3. PROVIDE DETAILS ON DRYER DUCTS. |
| | |
| | 4. SHOW SEQUENCE OF OPERATION FOR ATRIUM |
| | SMOKE EVAC AND CALCULATIONS OF AIR |
| | FLOW. |
| | |
| | 5. CHILLER ROOM REFRIGERANT RELIEF PIPE |
| | TO COMPLY WITH 2001 FBC(M) 1105.9 |
| | PUSH BUTTON SILENCE ON REFRIGERANT |
| | LEAK DETECTOR MODULE SHALL NOT BE |
| | AVAILABLE. |
| | HORN AND STROBE SHALL BE VISIBLE AND |
| | AUDIBLE THOUGHOUT ENTIRE ROOM WITH |
| | EQUIPMENT RUNNING. |
| | SIGN IN NOTE 22 TO BE BY EVERY DOOR |
| | INTO CHILLER ROOM. |
| | BREATHING APPERATUS TO BE CLOSE TO |
| | MAIN ACCESS DOOR. |
| | SET POINT FOR ALARM AND EMERGENCY |
| | VENTILATION SHALL BE MINIMUM 1000PPM |
| | PER TABLE 1103.1 |
| | IS THE REFRIGERANT PURGE EXHAUST |
| | FAN TO RUN CONTINUOUSLY? |
| | |
| | 6. SEE 2001 FBC(M) 1206.1.1 FOR |
| | PROHIBITED TEE APPLICATIONS. "FLUID IN |
| | THE SUPPLY SIDE OF A HYDRONIC SYSTEM |
| | SHALL NOT ENTER A TEE FITTING THROUGH |
| | THE BRANCH OPENING." |
| | |
| | 7. FLORIDA ENERGY CODE REQUIRES MINIMUM |
| | IPLV NOT SHOWN AS NPLV. PLEASE PROVIDE |
| | IPLV SHOWING COMPLIANCE WITH TABLE 4-5 |
| | |
| | 8. ROOF MOUNTED EQUIPMENT SUPPORTS |
| | HEIGHT IS BASED ON EQUIPMENT WIDTH PER |
| | TABLE 1511.7 2001 FBC. |
| | |
| | 9. THE PLANS PROVIDED ARE NOT A COMPLETE |
| | SET AND FOLLOWING REVIEWS COULD REFLECT |
| | COMMENTS ON ITEMS NOT APPARENT UNDER |
| | THIS INCOMPLETE PLAN SET. |
| | PLANS ARE REQUIRED TO BE SIGNED AND |
| | SEALED BY THE DESIGNER. |