| 2002-06-20 00:00:00 | 1) ANY NEW SECURITY GATES ARE TO BE |
| | PROPERLY PERMITTED. PROVISIONS ARE TO |
| | BE MADE FOR FIRE AND PARAMEDICAL |
| | ACCESS THRU THE GATES. IF THE GATES |
| | ARE ELECTRIC, PROVISIONS ARE TO BE MADE |
| | IN THE EVENT OF LOSS OF POWER. |
| | |
| | 2) ALL INGRESS LANES ARE TO BE AT LEAST |
| | 20 FEET IN CLEAR WIDTH. |
| | |
| | 3) PLEASE INDENTIFY ON THE PLANS THE |
| | REQUIRED FIRE LANE LOCATIONS. |
| | |
| | 4) WET FIRE HYDRANTS ARE REQUIRED PRIOR |
| | TO, DURING AND AFTER CONSTRUCTION. |
| | |
| | 5) WILL THE GUARDHOUSE BE STAFFED FULL |
| | TIME OR PART TIME. |
| | |
| | 6) SUITABLE FIRE HYDRANTS ARE TO BE |
| | PROVIDED FOR FIRE AND PARAMEDICAL |
| | EQUIPMENT DURING CONSTRUCTION. |
| | |
| | 7) TEMPORARY STANDPIPE SYSTEMS ARE |
| | REQUIRED DURING CONSTRUCTION. |
| | |
| | 8) IT APPEARS THAT ADDITIONAL FIRE |
| | HYDRANTS APPEAR TO BE NEEDED NEAR THE |
| | PROPOSED RESIDENTIAL BUILDING. |
| | |
| | 9) VALVES TO FIRE HYDRANTS ARE TO BE |
| | NO FARTHER THAN FOUR FEET TO THEM. |
| | |
| | 10) NEW FIRE HYDRANTS ARE TO BE PROVIDED |
| | WITH SEVEN AND HALF FEET CLEARANCE |
| | TO THE FRONT AND SIDES OF THEM. |
| | CLEARANCE OF AT LEAST FOUR FEET IS TO |
| | BE PROVIDED TO THE REAR OF THEM. |
| | |
| | 11) TAMPER SWITCHES, CHAINS AND LOCKS |
| | ARE REQUIRED ON THE BACKFLOW DEVICES. |
| | |
| | 12) PLEASE INDICATE INTERIOR FINISH |
| | CLASSIFICATION INFOMATION FOR WALLS |
| | AND CEILINGS. |
| | |
| | 13) KNOX-BOXES WILL BE REQUIRED FOR THE |
| | BUILDING. |
| | |
| | 14) PLEASE PROVIDE PRESCRIPTIVE CODE |
| | REQUIREMENTS FOR ALUMINUM RAIL SYSTEM. |
| | |
| | 15) EIFS COPING TRIM NOTED ON THE PLANS. |
| | PLEASE PROVIDE FLAME SPREAD DETAILS. |
| | |
| | 16) PLEASE PROVIDE TRAVEL DISTANCES, |
| | COMMON PATHS OF TRAVEL, DEAD-END |
| | CORRIDORS ON THE LIFE SAFETY PLANS. |
| | |
| | 17) ALL SHAFTWAYS THAT PERSONS CAN |
| | ENTER MUST BE MARKED "SHAFTWAY" IN |
| | RED LETTERS ON A WHITE BACKGROUND. |
| | |
| | 18) SIGNS REQUIRED IN STAIRWELLS |
| | INDICATING STAIR NUMBER, TERMINUS, |
| | FLOOR LEVEL, ETC. |
| | |
| | 19) AUTOMATIC SLIDING DOOR ASSEMBLIES |
| | TO COMPLY WITH APPLICABLE FIRE CODE |
| | REQUIREMENTS. |
| | |
| | 20) LOCKS ON EXIT DOORS SHALL NOT |
| | REQUIRE THE USE OF A KEY, TOOL, |
| | SPECIAL KNOWLEDGE OR EFFORT. IF |
| | PERMITTED, DELAYED EGRESS OR ACCESS |
| | CONTROLLED LOCKS WILL BE ALLOWED. |
| | |
| | 21) PORTECOCHERS'S IF FIRE AND |
| | PARAMEDICAL EQUIPMENT ARE EXPECTED TO |
| | PASS UNDERNEATH MUST BE AT LEAST |
| | THIRTEEN FEET SIX INCHES HIGH. |
| | |
| | 22) IS THE DOOR IN MEDICAL CLINIC C134 |
| | NEAR MITZVAH STORAGE C115 SWINGING IN |
| | THE RIGHT DIRECTION. |
| | |
| | 23) ELECTRICAL PAGES AND LIFE SAFETY |
| | PLANS DO NOT MATCH WITH REGARDS TO |
| | EXIT SIGN LOCATIONS. |
| | |
| | 24) MORE DETAILS REQUIRED ON FIRE PUMP. |
| | |
| | 25) MORE DETAILS REQUIRED ON EMERGENCY |
| | GENERATOR. |
| | |
| | 26) ELEVATORS TO COMPLY WITH 61C-5. |
| | |
| | 27) FIRE PROTECTION NOTES # 9 INDICATES |
| | SIX SPARE FIRE SPRINKLER HEADS WILL |
| | BE PROVIDED. SIX SPARE SPRINKLER HEADS |
| | ARE WHEN THREE HUNDRED FIRE SPRINKLERS |
| | OR LESS ARE USED. |
| | |
| | 28) FIRE SPRINKLER PLANS ARE INCOMPLETE. |
| | PLEASE PROVIDE COMPLETE FIRE SPRINKLER |
| | PLANS. NO FIRE DEPARTMENT CONNECTION'S |
| | ARE SHOWN. |
| | |
| | 29) FIRE STANDPIPE INFORMATION MISSING |
| | FROM PLANS. PLEASE PROVIDE STANDPIPE |
| | RISER DIAGRAMS. |
| | |
| | 30) HOW WILL THE BUILDING BE LICENSED. |
| | WILL IT BE RESIDENTIAL APARTMENTS, |
| | ADULT CONGREGATE LIVING FACILITY. PLEASE |
| | ADVISE. |
| | |
| | 31) VISIBLE FIRE ALARM DEVICES ARE |
| | REQUIRED WITHIN APARTMENTS DESIGNED FOR |
| | THE HEARING IMPAIRED. |
| | |
| | 32) ASSEMBLY ROOMS SUBJECT TO AN |
| | OCCUPANCY OF 100 OR MORE PERSONS MUST |
| | BE PROVIDED WITH PANIC HARDWARE ON THE |
| | EXIT DOORS. |
| | |
| | 33) PLEASE PROVIDE DETAILS ON SERVICE |
| | TYPE SHAFTS. |
| | |
| | 34) FIRE HYDRANTS ARE TO BE LOCATED |
| | WITHIN 150 FEET OF FIRE DEPARTMENT |
| | CONNECTIONS. |
| | |
| | 35) SEVERAL PAGES OF PLANS ARE NOT |
| | SIGNED AND SEALED. |
| | |
| | MIKE CARSILLO, ASSISTANT FIRE MARSHAL |
| | 659-8096,EXT.8497 |