| 2002-07-12 00:00:00 | **************** UNSAT *************** |
| | |
| | 1)NOTE: PLEASE NOTE SOME MISSING RECEPTS |
| | PER 210-52. |
| | |
| | 2)NOTE: PLEASE NOTE THAT SOME ELECTRICAL |
| | PANELS ARE SHOWN IN BATHROOMS. PLEASE |
| | NOTE THIS IS NOT PERMITTED PER 240-24 |
| | |
| | 3)NOTE: PLEASE SEE 110-26/384-7 FOR |
| | INSTALLATION OF PANELS IN STORAGE AREAS. |
| | PLEASE HAVE DEDICATED ELECTRICAL SPACE |
| | SHOWN ON PLANS. |
| | PLEASE NOTE THIS INCLUDES ALL PANELS AS |
| | SHOWN IN STORAGE ROOMS. |
| | |
| | 4)NOTE: PLEASE NOTE SOME MISSING RECEPTS |
| | PER 210-52H |
| | |
| | 5)NOTE: PLEASENOTE LABELING OF EQUIP- |
| | -MENT FOR ELECTRICAL ROOM LAYOUT. PLEASE |
| | NOTE MORETHAN ONE PANEL/TRANS ALL BEING |
| | SHOWN AS "X"??. |
| | |
| | 6)NOTE: PLEASE NOTE GROUNDING OF ALL |
| | TRANSFORMERS NEED TOMORE DETAILED? |
| | PER 250-30 |
| | |
| | 7)NOTE: PLEASE SHOW AMPERAGE DESIGNATION |
| | -S ON LINE DIAGRAM. PLEASE NOTE THAT IN |
| | ORDER TO VERIFY WIRE SIZES YOU WOULD |
| | HAVE TO TURN PAGES ABCK AND FORTH FOR |
| | EACH PANEL AND OR PIECE OF EQUIPMENT. |
| | |
| | 8)NOTE: PLEASE SHOW TRANSFORMER INFORMA- |
| | TION ON LINE DIAGRAM ALSO. |
| | |
| | 9)NOTE: PLEASE NOTE THAT E-206 NEEDS TO |
| | SHOW LAYOUT OF EQUIPMENT IN MAIN |
| | ELECTRICAL ROOM AND GENERATOR ROOM. |
| | |
| | 10)NOTE: PLEASE SHOW HOW MDPL AND MDPH |
| | ARE BEING FED? FROM FPL? |
| | |
| | 11)NOTE: PLEASE NOTE MDP`S ARE SHOWN AS |
| | 277V/480 AND NO INFORMATION ON GFI |
| | PROTECTION, 230-95 ETC. |
| | |
| | 12)NOTE: PLEASE NOTE NOT ENOUGH INFOR- |
| | -MATION FOR FIRE PUMP/SIZE/OCP ETC,,,, |
| | |
| | 13)NOTE: PLEASE NOTE MISSING DISC MEANS |
| | ON LOAD SIDE OF TRANSFORMERS.240-21/ |
| | 384-16,,, |
| | |
| | 14)NOTE: PLEASE NOTE TAPS ON LOAD SIDE |
| | OF ALL TRANSFORMERS. 240-21 |
| | |
| | 15)NOTE: PLEASE NOTE NOTHING SUBMITTED |
| | FOR GUARD HOUSE? GROUNDING? DISC MEANS |
| | 225-31/250-32 |
| | |
| | 16)NOTE: PLEASE NOTE THAT NO MAINS ARE |
| | SHOWN FOR MDPL/MDPH.230-71/230-72/230-2 |
| | |
| | 17)NOTE: PLEASE NOTE NO GROUNDING ELEC- |
| | -TRODE. SYSTEM DETAIL SUBMITTED . 250-50 |
| | |
| | 18)NOTE: PLEASE NOTE THAT NO LOAD |
| | CALCULATIONS WERE SUBMITTED.215-5 ETC |
| | 220-3,220-10,220-11,220-13,215-3,230-42 |
| | |
| | 19)NOTE: PLEASE SHOW WHERE FHAR 24 CFR |
| | 100.205 ARE SHOWN. |
| | |
| | 20)NOTE: PLEASE NOTE ARC FAULT FOR |
| | BEDRROMS.210-12 |
| | |
| | PLEASE NOTE THAT PLANS ARE NOT COMPLETE |
| | FOR FULL REVIEW. IF THERE ARE ANY QUESTI |
| | ONS, PLEASE CALL. |
| | |