Text |
| 2002-07-23 00:00:00 | PAID PLAN REVIEW.THE BUILDING WILL BE |
| | A THRESHOLD BUILDING AND WILL REQUIRE A |
| | THRESHOLD INSPECTOR AND A THRESHOLD |
| | INSPECTION PLAN.SEE FBC 105.13. |
| | CONTACT DON NEELY, ASSISTANT BUILDING |
| | OFFICIAL FOR ADDITIONAL INFORMATION |
| | REGARDING THRESHOLD BUILDINGS.(561) |
| | 659-8096 EXT, 8333. |
| | |
| | THE PLANS PROVIDED ARE NOT COMPLETE NOR |
| | WERE ANY SPECIFICATIONS INCLUDED, THUS |
| | ACOMPLETE, CLOSE AND CRITICAL PLAN |
| | REVIEW WAS NOT POSSIBLE.FBC 104.3.1.1 |
| | PROVIDES AN OUTLINE OF THE ITEMS |
| | REQUIERED FOR PLAN REVIEW AND CAN SERVE |
| | AS A GUIDE FOR THE BUILDING DESIGN |
| | PROFESSIONALS. |
| | |
| | THE BUILDING PROPOSES A MIXED OCCUPANCY |
| | GROUP OF R2, R4, B AND A2, USES.THE |
| | SITE PLAN DOES NOT INDICATE THE |
| | LOCATION OF THE FUTURE BLDG FOR |
| | DETERMINATION OF FBC TABLE 600 |
| | REQUIREMENTS. (ASSUMED PROPERTY LINE) |
| | |
| | SHEET A101, GENERAL NOTES #12.SEE FBC |
| | 803.2 FOR CLASSIFICATION OF INTERIOR |
| | FINISH. |
| | |
| | NOTES #13 AND #28, RE: FIRE PROTECTION |
| | AND FIRE STOPPING.SEE FBC 104.2.3 AND |
| | THE REQUIREMENT FOR SPECIFIC |
| | INFORMATION AS TO DESIGNS AND METHODS. |
| | |
| | SHEET LS- 1.01 HAS ERRONEOUS INFORMATION |
| | FOR THE RATINGS OF EXTERIOR BEARING |
| | WALLS.SEE FBC TABLE 600.(3HR) |
| | |
| | SIMILAR CONFLICTS EXIST WITH THE |
| | HEADING"BEAMS, GIRDERS AND ARCHES". |
| | |
| | LS - 1.01.AREAS SHOWN AS "B GROUP B" |
| | AND SUITES A AND B, DECLARE A SINGLE |
| | EXIT COMPLIANCE BASED ON AREA IN SQUARE |
| | FEET.SEE ALSO FBC 1004.1.2 AND FBC |
| | 1004.1.3 AS MAY BE APPLICABLE. |
| | |
| | SUITES A AND B ARE PRESENTED AS |
| | "INDIVIDUAL" IT THEN FOLLOWS THAT |
| | CORRIDOR 134 IS A DEAD END IN EXCESS OF |
| | FIFTY FEET AND IS PROHIBITTED BY FBC |
| | 1004.1.4. |
| | |
| | DOORS SHOWN AS C176, C177 AT THE PRIVATE |
| | DINING ROOM ARE NOT RATED AS REQUIRED |
| | FOR ATRIUM SEPARATION. |
| | |
| | A PARTITION DETAIL FOR THE NON-RATED |
| | SMOKE PARTITIONS SHOULD BE PROVIDED IN |
| | ACCORDANCE WITH FBC TABLE 704.2.4, |
| | FOOTNOTE #4. |
| | |
| | A SEATING PLAN IS NECESSARY FOR THE |
| | DINING, MULTI USE, AND SIMILAR ROOMS. |
| | SEE FBC 1003.1.2. |
| | |
| | PROVIDE CALCULATIONS FOR THE ATRIUMS, |
| | AND AN NARRATIVE OF THE OPERATION. |
| | INCLUDE A DESCIPTION OF COMPLIANCE WITH |
| | FBC 414.8 FOR THE INTERIOR ROOMS. |
| | |
| | FBC TABLE 410.2.2 REQUIRES ONE HOUR |
| | SEPARATION FOR THE MAINTENANCE ROOM |
| | #A144. |
| | |
| | THE RAMP IN ROOM C157, FOR THE PLATFORM, |
| | MUST COMPLY WITH FBC 11-4.8, INCLUDING |
| | HANDRAILS. |
| | |
| | THE EIFS TRIM DEPICTED IN VARIOUS |
| | PLACESDOES NOT COMPLY WITH FBC 1404.1. |
| | |
| | THE STRUCTURAL PLANS ARE INCOMPLETE. |
| | HOW WAS THE 2500 PSF SOIL BEARING VALUE |
| | ARRIVED AT? |
| | |
| | PLEASE NOTE THE DESIGN STANDARDS USED, |
| | ASSUMED LOADS AND SPECIFIC INFORMATION |
| | FOE THE DELEGATED DESIGN ITEMS, |
| | INCLUDING, TRUSSES, HAND GUARD RAILS, |
| | STAIRS, ETC. |
| | |
| | THE ABOVE INFORMATION SHOULD BE |
| | ADDRESSED IN THE ACTUAL PERMIT PLANS |
| | AND SPECIFICATIONS. |