| Date |
Text |
| 2002-07-01 00:00:00 | DENIED |
| | |
| | 1. FAN COIL UNITS AND OTHER MECHANICAL |
| | EQUIPMENT TO BE LOCATED WITH RESPECT TO |
| | BUILDING CONSTRUCTION TO ALLOW FOR |
| | SERVICE, REPAIR OR REPLACEMENT |
| | |
| | 2. BATHROOM EXHAUST DUCTS TO HAVE FIRE |
| | DAMPERS OR FIRE SMOKE DAMPERS OR MEET |
| | ALL 4 EXCEPTIONS UNDER FBC(M) |
| | 607.1.3(3). |
| | |
| | 3. NO FIRE DAMPERS SHOWN ON PLAN. SHOW |
| | LOCATION OF ALL FIRE DAMPERS AND SMOKE |
| | FIRE DAMPERS AND PROVIDE INSTALLATION |
| | DETAILS PER 607.6 |
| | |
| | 4. DRYER INSTALLATION TO COMPLY WITH 504 |
| | |
| | 5. RANGE IN FOOD SERVICE AREA SHALL HAVE |
| | TYPE 1 HOOD PROVIDED PER 507. PROVIDE |
| | INFORMATION ON HOOD, DUCTWORK AND FIRE |
| | SUPPRESSION SYSTEM. SEPARATE PERMIT |
| | WITH PLANS WILL BE REQUIRED FOR |
| | INSTALLATION. |
| | |
| | 6. CLEARLY SHOW LOCATION OF DRYER VENT |
| | TERMINATION. |
| | |
| | 7. SHOW LOCATION OF OUTSIDE AIR INTAKES |
| | FOR OUTSIDE AIR UNITS WITH RESPECT TO |
| | EXHAUST FAN AND DRYER VENT TERMINATIONS. |
| | |
| | 8. FOOD SERVICE DRAWINGS INDICATED ON |
| | DRAWING LIST ARE MISSING FROM PLAN |
| | REVIEW SET. |
| | |
| | 9. PROVIDE INFORMATION ON EER OR IPLV OF |
| | OUTSIDE AIR EQUIPMENT. |
| | |
| | 10. PROVIDE OUTSIDE AIR CALCULATION |
| | SHOWING COMPLIANCE WITH FBC(M) TABLE |
| | 403.3 |