| 2002-06-24 00:00:00 | ************ UNSAT ****************** |
| | |
| | 1)NOTE: PLEASE NOTE MISSING GROUNDING |
| | ELECTRODE FOR DETACHED "GUARDHOUSE" |
| | 250-32. |
| | |
| | 2)NOTE: PLEASE NOTE PANELS SHOWN IN |
| | "STORAGE ROOM" ON E-102. PLEASE NOTE |
| | NO STORAGE PER 110-26/384-7 |
| | |
| | 3)NOTE: PLEASE NOTE PANELS SHOWN IN |
| | "STORAGE ROOM ON E-104 "D137". |
| | 110-26/384-7. |
| | |
| | 4)NOTE: PLEASE PROVIDE MORE DETAIL FOR |
| | GROUNDING OF TRANSFORMER AND PANEL "DP" |
| | ATTACHMENT ETC. 250-30 |
| | |
| | 5)NOTE: PLEASE NOTE NO LOAD CALCULATIONS |
| | WERE SUBMITTED? PER 220 |
| | |
| | 6)NOTE: PLEASE NOTE PANEL FOR GUARD |
| | HOUSE NOT SHOWN FOR WHERE FEED IS COMING |
| | FROM?? |
| | |
| | 7)NOTE: PLEASE NOTE PANEL DP NOTE SAYS |
| | COMING FROM MDP? PLEASE NOTE MDP NOT |
| | SHOWN/LOAD ETC ETC?? |
| | |
| | 8)NOTE: PLEASE CLARIFY PANELS LSH,EQ |
| | SHOWN AS MLO W/ MAIN BRKRS?? |
| | |
| | 9)NOTE: PLEASE CLARIFY HOW NOTE FOR |
| | EM LTS AND EXIT LTS SAYS COMING FROM EM |
| | PANEL AND NOTHING IS SUBMITTED FOR |
| | REVIEW FOR EM BACK UP POWER RISER? |
| | PLANS ALSO NOTE LSH/EQ COMING FROM |
| | OTHER LCOATIONS, BUT NO INFORMATION WAS |
| | SUBMITTED FOR REVIEW. LOAD CALCS FOR |
| | FEEDS FROM EXSITING??? |
| | |
| | PLEASE COMPLETE PLANS FOR COMPLETE |
| | REVIEW. PLEASE SUBMIT ABOVE INFORMATION |
| | FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |