| 2002-08-05 00:00:00 | COMMENTS FOR THE PAID PLAN PREVIEW, (NOT |
| | A PERMIT APPLICATION), FOR MORSE SENIOR |
| | CAMPUS. |
| | |
| | THE PLANS INDICATE A ONE STORY, GROUP I, |
| | UNRESTRAINED OCCUPANCY OF TYPE IV FIRE |
| | SPRINKLERED CONSTRUCTION, 29000 +/- |
| | SQUARE FEET IN AREA.THERE WERE NO |
| | SPECIFICATIONS BOOKS PROVIDED WITH THE |
| | PLANS. |
| | |
| | PLANS SUBMITTED FOR PERMIT ARE REQUIRED |
| | TO HAVE THE FIRE PROTECTION SYSTEMS |
| | DESIGN INCLUDED.FIRE SPRINKLERS, FIRE |
| | ALARM AND OTHER PERTINENT INFORMATION. |
| | SEE ALSO, FBC 409.1.1.1, AND 409.1.6, |
| | TOGETHER WITH CHAPTER 8 OF NFPA 13-99. |
| | |
| | SHOW THE TRAVEL DISTANCES ON THE LIFE |
| | SAFETY PLANS. SEE FBC 409.2.1. |
| | |
| | THE PLACEMENT OF THE DINING AREAS IN THE |
| | SPECIAL CARE UNITS DOES NOT COMPLY WITH |
| | FBC 1024.7.9. |
| | |
| | WITH THE PERMIT PLANS INCLUDE A |
| | PARTITION DETAIL DEPICTING THE |
| | REQUIREMENTS OF FBC 704.2.1.5 INCLUDING |
| | THE FIRE DESIGN NUMBER. |
| | |
| | THE CORRIDOR AND DOOR WIDTHS DO NOT |
| | COMPLY WITH FBC 1024.1.2. |
| | |
| | INCLUDE WITH THE PERMIT PLANS THE |
| | STRUCTURAL INFORMATION DECLARED IN FBC |
| | 1606.1.7 AND THE APPLICABLE INFORMATION |
| | FROM FBC 104.3.1.1. |
| | |
| | THE GROUP D OCCUPANCY APPEARS TO BE |
| | INCIDENTAL TO THE GROUP I OCCUPANCY AS |
| | PROVIDED FOR IN FBC 313.2.4. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY, THE PERMIT PLANS |
| | STAMPED BY THAT OFFICE, AND A COPY OF |
| | THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. |
| | CALL (561) 233-5025 FOR MORE INFORMATION |
| | |
| | ON PROJECTS OF THIS SCOPE THE BUILDING |
| | OFFICIAL REQUIRES A RESIDENT INSPECTOR. |
| | CONTACT DON NEELY, ASSISTANT BUILDING |
| | OFFICIAL FOR MORE INFORMATION.(561) |
| | 659-8096 EXT 8333. |
| | |
| | SHOW HOW THE GLAZED PORTIONS OF THE |
| | EXTERIOR WALLS AND ROOF WILL COMPLY |
| | WITH THE CITY'S HURRICANE MISSILE |
| | IMPACT RESISTANCE REQUIREMENTS.SEE |
| | THE ATTACHED INFORMTION. |
| | |
| | IF TEST REPORTS OR NOTICE OF ACCEPTANCE |
| | DATA FOR THE WINDOWS, DOORS AND ROOF |
| | COVERING ARE NOT INCLUDED WITH THE |
| | PERMIT APPLICATION, A SEPARATE PERMIT |
| | AND FEES WILL BE REQUIRED. |