| Plan Review Notes For Permit 02060361 |
| Permit Number |
02060361 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-07-06 00:00:00 | PLAN DENIED | | | 1) ENERGY CALCS AND PLANS DO NOT MATCH | | | ON A/C EQUIPMENT SEER | | | 2) NEED LETTER FROM MANUFACTURE STATING | | | THAT UNDER ANY CONDITION THE | | | AIRHANDLER WILL NOT PRODUCE 2000 CFM | | | 3) REFER TO SECTION 601.4 BALANCED | | | RETURN AIR | | | 4) VARIFY TYPE OF VENTILATION USED FOR | | | FRESH AIR SECTION 402 NATURAL OR | | | SECTION 403 MECHANICAL FBC.2001 | | | 5) CALCULATION FOR TYPE OF VENTILATION | | | USED | | | PLAN REVIEW BY HAROLD MOSER | | | (561)659-8096 EXT.8390 |
|