| Plan Review Notes For Permit 02060290 |
| Permit Number |
02060290 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2002-12-10 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION, MAKE NECESSARY CHANGES TO | | | PLANS, AND RESUBMIT FOR REVIEW WITH AS- | | | BUILTS,PRIOR TO ROUGH INSPECTION. | | | | | | 1} THE GARAGE OUTLETS ARE REQUIRED TO BE | | | GFI PER 210-8(A)(6). | | | | | | 2} PROVIDE AN EGRESS LIGHT FOR THE | | | GARAGE PER 210-70(A)(2). | | | | | | 3} PLEASE NOTE FRONT AND REAR | | | RECEPTS REQ`D PER 210-52E | | | | | | 4} THE SMOKE DETECTOR LOCATED IN THE | | | HALL MUST BE LOCATED AT MORE THAN | | | 3'FROM THE BATHROOM DOOR PER NFPA-72 | | | 8-1.4.2. | | | | | | 5} PLEASE LIST THE REQ'D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE OR NOTE ON PLANS FOR BRANCH | | | CIRCUIT PROTECTION. PER 210-12 | | | | | | 6} PLEASE NOTE KITCHEN COUNTER- | | | SPACE RECEPT SPACING SHALL MEET ART; | | | 210-52C 1,2,3,4,AND 5.AND 210-8(A)(6). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT 8392 |
|