| Date |
Text |
| 2002-09-04 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 02060289 |
| | ADD: 707 39TH ST (FRONT BUILD) |
| | CONT: KENACO DEV CORP INC |
| | TEL: (561)784-8618 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A |
| | DESCRIPTION OF THE REVISION MADE, IDEN- |
| | TIFYING THE SHEET OR SPECIFICATION PAGE |
| | WHERE THE CHANGES CAN BE FOUND, WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 1) WHAT OCCUPANCY USE WILL THIS BE? |
| | A) R-3 SINGLE FAMILY OCCUPANCY |
| | B) R-3 ROOMING HOUSE (NOT TRANSIENT) |
| | C) R-2 ROOMINGHOUSE (TRANSIENT) |
| | D) R-1 BOARDING HOUSE (TRANSIENT) |
| | |
| | 2) AS STATED IN THE OPENING STATEMENT, |
| | LIST WORK TO BE ACCOMPLISHED ON THE |
| | INTERIOR, AS WELL AS EXTERIOR. |
| | |
| | 3) 3401.7.2 REPAIRS AND ALTERATIONS, |
| | AFTER AN ACCURATE DESCRIPTION OF WORK |
| | THAT SHALL BE COMPLETED UNDER THIS PER- |
| | MIT ATRUE ASSESSMENT OF THE DOLLAR |
| | VALUE CAN BE DERIVED FOR WORKTO BE PER- |
| | MITTED. THIS SECTION OF THE CODE DETER- |
| | MINES AS TO WHAT SHALL BE REQUIRED TO BE |
| | BROUGHT UP TO CODE BY THE PERCENT OF |
| | WORK ACCOMPLISHED (DOLLAR VALUE) VS THE |
| | VALUE OF THE EXISING BUILDING. |
| | |
| | 4) 1203.2.5 KITCHENS SHALL BE NO LESS |
| | THAN 7 FT IN ANY DIRECTION. |
| | |
| | 5) 1203.4.1 TOLIET ROOMS SHALL NOT OPEN |
| | DIRECTLY INTO A ROOM USED FOR THE PREP- |
| | ARATION OF FOOD FOR SERVICE TO THE |
| | PUBLIC. OCCUPANCY USE SHALL DETERMINE |
| | IF THIS SECTION IS APPLICABLE. |
| | |
| | 6) MISSING PRODUCT TESTING REPORTS FOR |
| | ALL EXTERIOR DOORS & GLAZED OPENINGS. |
| | 2 SETS OF PRODUCT TESTING REPORTS ARE |
| | REQUIRED FOR EACH BUILDING, SINCE THEY |
| | ARE UNDER SEPERATE PERMIT!!!!!!! |
| | |
| | 7) 1007.4.2 STAIRS SHALL HAVE FLOORS OR |
| | LANDINGS AT DOOR OPENINGS. MISSING AT |
| | THE FRONT ENTRY AND FIRST FLOOR PROPOSED |
| | KITCHEN. |
| | |
| | 8) 1007.5.1 HANDRAILS REQUIRED FOR |
| | STAIRWAY, GRIPPING SURFACES SHALL BE |
| | CONTINUOUS, WITHOUT INTERRUPTION BY |
| | NEWEL POST OR OTHER OBSTRUCTIONS. |
| | |
| | 9) 1007.5.5 HANDRAILS SHALL EXTEND AT |
| | LEAST 12" HORIZONTALLY BEYOND THE TOP |
| | RISER OF A FLIGHT . AT THE BOTTOM, THE |
| | HANDRAIL SHALL BE CONTINUE TO THE SLOPE |
| | FOR A DISTANCE OF THE DEPTH OF ONE TREAD |
| | FROM THE BOTTOM RISER. EXCEPTION, |
| | HANDRAILS IN A DWELLING UNIT. OCCUPANCY |
| | SUB-CLASSIFICATION SHALL DETERMINE! |
| | |
| | 10) UPPER FLOOR PLAN IS THE DETAIL FOR A |
| | "ALTERNATE KITCHEN" TO BE USED FOR THE |
| | SECOND FLOOR MAKING 2 KITHENS FOR THIS |
| | BUILDING? |
| | |
| | PLANS ARE NOT THROUGH ENOUGH TO DO A |
| | COMPLETE REVIEW. PLEASE ADDRESS THE |
| | ABOVE ISSUES. BECAUSE OF NOT ANSWERING |
| | THE SAME COMMENTS FROM THE FIRST REVIEW |
| | ADDITIONAL COMMENTS MAY APPEAR FOR THE |
| | FIRST TIME ON THE NEXT REVIEW!!!! |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096 X 8412 |