| Plan Review Notes For Permit 02060289 |
| Permit Number |
02060289 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-11 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE ANY NECESSARY CHANGES | | | IN THE DRAWINGS AND RESUBMIT FOR REVIEW. | | | | | | 1} THE PLANS CONTAIN SHEETS WITH | | | ENGINEERS SEAL BUT NO TITLE | | | BLOCK.PLEASE COMPLY WITH FAC | | | 61G15-23.002(2). | | | | | | 2} PLEASE LIST THE REQ`D ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE PER 210-12. | | | | | | 3} THERE ARE PANEL SCHEDULES AND RISER | | | DIAGRAMS IN TWO SEPERATE LOCATIONS ON | | | THE PLANS,PLEASE REMOVE THE ONES NOT | | | INTENDED FOR REVIEW. | | | | | | 4} PLEASE INDICATE THE INTENDED SCOPE | | | OFWORK UNDER THIS (THESE) PERMIT(S)? | | | A) WHY ARE THERE TWO PERMITS FOR THIS | | | WORK? | | | B) WHAT ELECTRICAL WORK IS NEW AND | | | WHAT IS EXISTING? IS THERE ELECTRICAL | | | WORK TO BE DONE IN THE ROOMS LABELED | | | "TO BE REPAIRED"? PLEASE CLARIFY. | | | | | | 5} THERE IS NO SMOKE DETECTORS SHOWN ON | | | PLAN,PLEASE CLARIFY. | | | | | | 6} EGRESS LIGHTING IS LABELED GFI? | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT. 8392 |
|