| 2002-06-18 00:00:00 | *********** REVISION NEEDED ********** | | | | | | 1)NOTE: PLEASE NOTE ITEMS REDLINED ON | | | PLANS. | | | MISSING RECEPTS PER 210-52/210-52-C-1/ | | | 210-52H/ ETC. ETC. | | | PLEASE NOTE MISSING EQUIPMENT GROUNDING | | | CONDUCTOR BETWEEN MAIN DISC AND PANEL. | | | SIZE PER 250-122 | | | | | | PLEASE SUBMIT THE REVISED PLANS BEFORE | | | FINAL ELECTRICAL INSPECTION IS CALLED | | | IN. IF THERE ARE ANY QUESTIONS, PLEASE | | | CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|