| Plan Review Notes For Permit 02060280 |
| Permit Number |
02060280 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-18 00:00:00 | ************* REVISION NEEDED ******** | | | | | | 1)NOTE: PLEASE NOTE PLANS WERE REDLINED | | | WITH MANY OF THE FOLLOWING MISSING. | | | | | | HALLWAY MASTER BED RM 210-52H | | | RECEPT MASTER BATH 3' MIN 210-52D | | | MISSING MANY RECEPTS PER 210-52 | | | MISSING KITCHEN COUNTERSPACE 210-52-C-1 | | | MISSING REAR RECEPT. 210-52E | | | MISSING EQUIPMENT GROUNDING BETWEEM MAIN | | | DISC AND PANEL. | | | | | | PLEASE HAVE ALL OF THE ABOVE REVISED | | | BEFORE FINAL ELECTRICAL INSPECTION IS | | | CALLED IN. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|