| Date |
Text |
| 2002-06-18 00:00:00 | **************** UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM, |
| | PANEL SCHEDULE,LOAD CALCULATIONS, DO NOT |
| | CORRELATE. 180A , 200A, 300A??? SHOWN IN |
| | DIFFERENT LOCATIONS?? |
| | |
| | 2)NOTE: PLEASE NOTE THAT THERE ARE FOUR |
| | SMALL APPL CIRCUITS SHOWN IN LOAD CALCS |
| | AND ONLY TWO ON PANEL SCHEDULE? |
| | |
| | 3)NOTE: PLEASE NOTE LOAD FOR AHU HEAT IS |
| | SHOWN AT 10KW AND HAS AN OCP OF 50A? |
| | PLEASE SEE SIZING OF OCP PER 424-3-B |
| | |
| | 4)NOTE: PLEASE NOTE LAYOUT FOR HOUSE |
| | DOES NOT CORRELATE WITH MECH PLAN? |
| | WHICH ONE? PLEASE SHOW COND UNITS AND |
| | AHU`S ON ELECTRICAL PLAN WITH REQ`D DISC |
| | `S PER 440-11. |
| | |
| | 5)NOTE: PLEASE NOTE DEPENDING ON WHAT |
| | SIZE OF OCP IS FINALLY SHOWN , PLEASE |
| | SIZE SERVICE ENTRANCE CONDUCTORS. PLEASE |
| | ALSO NOTE/CLARIFY (4) CONDUCTORS FROM |
| | METER TO PANEL FOR SINGLE PHASE SERVICE. |
| | PLEASE CLARIFY. |
| | |
| | 6)NOTE: PLEASE SHOW AND SIZE GROUNDING |
| | ELECTRODE CONDUCTOR PER 250-66. |
| | |
| | 7)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW EQUIPMENT BEING INSTALLED. |
| | MAINS/PANELS/BREAKERS MUST BE RATED FOR |
| | THE AVAILABLE FAULT CURRENT PER 110-9. |
| | |
| | 8) NOTE: PLEASE SHOW ALL OUTLET SPACING |
| | TO MEET 2`,6`,12` RULE PER 210-52. |
| | MISSING ONLY A COUPLE. |
| | |
| | 9)NOTE: PLEASE NOTE MISSING SD OUTSIDE |
| | BR#2. |
| | |
| | 10)NOTE:PLEASE CLARIFY IF A 42 CIRCUIT |
| | PANEL IS 200A OR 225A?? |
| | |
| | 11)NOTE: PLEASE NOTE MIN KVA FOR LAUNDRY |
| | CIRCUIT SHALL BE 1500W. PLEASE REVISE |
| | |
| | 12)NOTE: PLEASE NOTE POOL EQUIPMENT IS |
| | SHOWN AT 4500W AND SHOWN ON PANEL SCHED- |
| | -ULE AS 20A AND #12AWG?? PLEASE CLARIFY. |
| | |
| | 13)NOTE: PLEASE NOTE, NOTE BELOW PANEL |
| | SCH, MENTIONS, USE "TW" FOR LARGER THAN |
| | #8?? PLEASE SEE NEC IN MANY LOCATIONS |
| | FOR USE OF "TW" PLEASE ALSO NOTE SIZING |
| | OF CONDUCTORS PER 60 DEGREE RATINGS PER |
| | 310-16. MOST OF WIRING USED TODAY IS |
| | NOT TW. |
| | |
| | 14)NOTE: PLEASE CLARIFY SQ FT OF HOUSE, |
| | LOAD CALCS SHOW 6775 AND COVER SHEET |
| | SHOWS 6034? |
| | |
| | 15)NOTE: PLEASE NOTE ELECTRICAL PLAN |
| | SHOWN FOR SECOND FLOOR IS NOT CLEAR WITH |
| | ALL BLDG SPECS PRINTED OVER. PLEASE ALSO |
| | NOTE PRINTING SEEMS TO HAVE MISSED PART. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE NAY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-659-8096 EXT 8372 |