Plan Review Notes
Plan Review Notes For Permit 02060265
Permit Number 02060265
Review Stop E
Sequence Number 1
Notes
Date Text
2002-06-12 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE NOTE AND COMPLY WITH THE
 FOLLOWING BEFORE CALLING FOR INSPECTION:
  
 1} SMOKE DETECTORS TO BE INSTALLED PER
 2-2.1.1.1 & 2-2.2.1 NFPA-72.
  
 2} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12, AND WIRE ROOMS
 ACCORDINGLY.
  
 3} INSTALL RECEPTACLES TO COMPLY WITH
 ARTICLES 210-52(A)(1) & 210-52(A)(1)(A).
  
 4} THE LOAD CALCULATIONS ON THE PLANS
 SHOW A TOTAL OF 182 AMPS,BUT THERE IS NO
 INDICATION OF THE PANEL RATING OR
 OVER-CURRENT PROTECTION.THE RATINGS
 MUST BE AT LEAST 200 AMPS.
  
 5} PLEASE NOTE AN ADDITIONAL PERMIT IS
 REQUIRED FOR THE NEW A/C SYSTEM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT. 8392