| Plan Review Notes For Permit 02060227 |
| Permit Number |
02060227 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2002-07-10 00:00:00 | 1) A MINIMUM OF 10 FEET CLEARANCE IS | | | REQUIRED FROM THE DUCT TO OTHER | | | PORTIONS OF THE BUILDING. | | | | | | 2) A MINIMUM OF AT LEAST 1500 CFM IS | | | REQUIRED FROM THE EXHAUST FAN. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|