| Plan Review Notes For Permit 02060227 |
| Permit Number |
02060227 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-07 00:00:00 | *******************DENIED*************** | | | | | | PLEASE PROVIDE MANUFACTURER INSTALLATION | | | INSTRUCTIONS FOR THE 3M FIREMASTER (OR | | | EQUAL). | | | | | | PLAN SHEET 1 OF 1 EXHUAST FAN INDICATES | | | 1200 CFM AT .75 STATIC PRESSURE?WITH A | | | 10 X 10 DUCT, EXHAUST FAN W/1200 CFM | | | FIGURED ON THE DUCTULATOR DOES NOT SHOW | | | .75 STATIC PRESSURE.PLEASE CLARIFY. | | | | | | PLEASE NOTE MAKE UP AIR SHALL NOT | | | DECREASE THE COMFORT CONDITIONS OF THE | | | OCCUPIED SPACE AS PER 2001 FBC(M) | | | 508.1.1. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|