| Plan Review Notes For Permit 02060193 |
| Permit Number |
02060193 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2002-06-07 00:00:00 | 1) THE PROPOSED DESIGN TO ELIMINATE | | | AN EXISTING CODE VIOLATION IS NOT | | | ACCEPTABLE. THE FIRE CODE REQUIRES | | | THAT THE ONLY OPENINGS WITHIN AN | | | EXIT ENCLOSURE IS DUCTWORK USED TO | | | SUPPLY STAIR PRESSURIZATION SYSTEMS. | | | PLEASE REVISE DESIGN. RE: NFPA 101, | | | THE LIFE SAFETY CODE, 2000 EDITION, | | | SECTION 7.1.3.2.1, (E). | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|