2003-05-23 00:00:00PROVISO
 ~~~~~~~
 THIS REVISION IS PASSED UNDER THE
 CONDITION THAT THERE IS A MEANS OF
 DISCONNECTING ALL SERVICE CONDUCTORS
 BEFORE THEY ENTER THE BUILDING,OR THEY
 MEET THE CONDITIONS OF ARTICLE 240-6.
  
 A REVISED DRAWING SHOWING TYPE OF
 INSTALLATION SHALL BE RESUBMITTED FOR
 REVIEW PRIOR TO A ROUGH INSPECTION OF
 THIS SERVICE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718