2003-04-11 00:00:00********** UNSAT ****************
  
 1)NOTE: PLEASE SEE RISER, PLANS STILL
 SHOW A 1000A METER CAN. PLEASE VERIFY
 SIZE AND IF NOT CT CAN.
  
 2)NOTE: PLEASE SEE SERVICE ENTRANCE
 CONDUCTORS, STILL SHOWN AS 9- 400MCM
 IN 3-SETS OF 3" CONDUITS. THIS WOULD
 BE 9045A`S WORTH OF WIRE.
  
 3)NOTE: PLEASE NOTE, AS PER INSTALLATION
 AT JOBSITE, A COMPLETE ENVELOPE OF
 CONDUIT/CONDUCTORS INTO BLDG HAS NOT
 BEEN ACHIEVED. IT IS PLAN REVIEWS UNDER-
 -STANDING THAT A GUTTER(S) HAS BEEN
 INSTALLED. PLEASE VERIFY AND CLARIFY
 HOW CODE WILL BE MET W/ OUT HAVING
 UNPROTECTED CONDUCTORS "INSIDE" BLDG
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  