| Plan Review Notes For Permit 02060115 |
| Permit Number |
02060115 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2003-04-11 00:00:00 | ********** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE RISER, PLANS STILL | | | SHOW A 1000A METER CAN. PLEASE VERIFY | | | SIZE AND IF NOT CT CAN. | | | | | | 2)NOTE: PLEASE SEE SERVICE ENTRANCE | | | CONDUCTORS, STILL SHOWN AS 9- 400MCM | | | IN 3-SETS OF 3" CONDUITS. THIS WOULD | | | BE 9045A`S WORTH OF WIRE. | | | | | | 3)NOTE: PLEASE NOTE, AS PER INSTALLATION | | | AT JOBSITE, A COMPLETE ENVELOPE OF | | | CONDUIT/CONDUCTORS INTO BLDG HAS NOT | | | BEEN ACHIEVED. IT IS PLAN REVIEWS UNDER- | | | -STANDING THAT A GUTTER(S) HAS BEEN | | | INSTALLED. PLEASE VERIFY AND CLARIFY | | | HOW CODE WILL BE MET W/ OUT HAVING | | | UNPROTECTED CONDUCTORS "INSIDE" BLDG | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 | | | [email protected] |
|