| Plan Review Notes For Permit 02060115 |
| Permit Number |
02060115 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2002-10-23 00:00:00 | PROVISO:MECHANICAL PERMIT 02081954 | | | | | | PLAN SHEET M3.1 DETAIL 9, "CONDENSING | | | UNIT MOUNTING DETAIL" - PLEASE NOTE AS | | | PER 2001 FBC 1511.7 ROOF MOUNTED | | | MECHANICAL UNITS SHALL BE MOUNTED ON | | | CURBS RAISED A MINIMUM OF 8 INCHES ABOVE | | | THE ROOF SURFACE OR WHERE ROOFING | | | MATERIALS EXTEND BENEATH THE UNIT, ON | | | RAISED EQUIPMENT SUPPORTS PROVIDING A | | | MINIMUM CLEARANCE HEIGHT IN ACCORDANCE | | | WITH TABLE 1511.7.SEE ATTACHED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|