2002-10-23 00:00:00PROVISO:MECHANICAL PERMIT 02081954
  
 PLAN SHEET M3.1 DETAIL 9, "CONDENSING
 UNIT MOUNTING DETAIL" - PLEASE NOTE AS
 PER 2001 FBC 1511.7 ROOF MOUNTED
 MECHANICAL UNITS SHALL BE MOUNTED ON
 CURBS RAISED A MINIMUM OF 8 INCHES ABOVE
 THE ROOF SURFACE OR WHERE ROOFING
 MATERIALS EXTEND BENEATH THE UNIT, ON
 RAISED EQUIPMENT SUPPORTS PROVIDING A
 MINIMUM CLEARANCE HEIGHT IN ACCORDANCE
 WITH TABLE 1511.7.SEE ATTACHED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.