Plan Review Notes
Plan Review Notes For Permit 02060115
Permit Number 02060115
Review Stop E
Sequence Number 3
Notes
Date Text
2002-10-18 00:00:00************** UNSAT****************
  
  
 1)NOTE: PLEASE NOTE FOOTER STEEL IS
 NOT SHOWN AS A PART OF THE GROUNDING
 ELECTRODE SYSTEM. 250-50 REQ`D.
  
 2)NOTE: PLEASE NOTE PANEL LP-2 SHOWS A
 500A MAIN BRKR ALONG WITH A 400A MAIN
 BRKR. THIS WAS NOTED ON PREVIOUS REVIEW.
 RESPONSE MENTIONS, SHOWN AS 400A. PLEASE
 SEE E6.2. LETTER DATED 9/30/02 #6
  
 3)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 STILL SHOWS GROUNDING ELECTRODE SYSTEM
 COMING FROM "LP-1", PLEASE SEE 250-24
 FOR CONNECTION POINT.
  
 4)NOTE: PLEASE SEE RESPONSE LETTER FROM
 ZEIDLER GRINNELL, DATED SEPT 30TH, 2002
 PLEASE SEE RESP. #3 MENTIONS TO SEE
 LOADS FOR TRACK LIGHTING IS SHOWN ON
 LPZ? PLEASE CLARIFY. PLEASE ALSO NOTE
 PANELS OR LOAD CALCS JUST NEED TO SHOW
 LOADING FIGURED FOR TRACK. PLANS SHOW
 LOADS CONNECTED. PLEASE CLARIFY HOW THIS
 CLARIFIES HOW MUCH LOAD PER FT WAS GIVEN
 ?
  
 5)NOTE: PLEASE SEE NOTE RESPONSE#5
 LETTER DATED 9/30/02. NOTE MENTIONS
 CHANGING 150A BRKR TO 225A, PLEASE SEE
 FEEDER NOTE #10 ON RISER DIAGRAM WHICH
 REFERS TO FEEDER SCHEDULE ON E5.2,,
 PLEASE NOTE, FEEDERS SHOWN AT 1/0`S
 PLEASE CORRELATE AND REVISE.
  
 6)NOTE: PLEASE SEE LETTER ATTACHED,
 PLEASE SEE FS 553.80(2)(B) WITH RESPECT
 TO DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONALS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICA PLAN REVIEW
 561-659-8096 EXT 8372