3 |
|
| Notes |
| Date |
Text |
| 2002-10-22 00:00:00 | PROVISO: ROOF BILCO HATCH, PRODUCT TEST- | | | ING REPORT SHALL BE REQUIRED BEFORE THE | | | ROOF METAL TIN TAG INSPECTION (112). | | | IF PRODUCT TESTING REPORT IS NOT LOCATED | | | THEN SITE SPECIFIC ENGINEERING FOR WIND | | | SHALL BE REQUIRED. WIND CALCULATIONS | | | SHALL BE FOR 140 MPH WIND ZONE | | | (3 SECOND GUST). IF THE HATCH HAS A | | | GLAZED OPENING IN THE LID AND LESS THAN | | | 30' ABOVE GRADE, LARGE MISSLE IMPACT | | | TESTING SHALL ALSO BE CONSIDERED! | | | BUILDING PLAN REVIEW | | | JIM WITMER |
|